UPS5000-H-1200 kVA
User Manual (100 kVA Power Modules)
8 Technical Specifications
Issue 01 (2020-07-15)
Copyright © Huawei Technologies Co., Ltd.
160
8
Technical Specifications
Table 8-1
Physical specifications
Item
Specifications
Cabling mode
Battery cables are routed in and out from the top, and input
and output cables are connected using the busway.
IP rating
IP20
Communication
Supports dry contacts, RS485 ports, and FE ports. Supports
SNMP and Modbus.
Dimensions (H x W x D)
2200 mm x 1600 mm x 1000 mm
Weight
1497 kg
Table 8-2
Environmental specifications
Item
Specifications
Operating temperature
0°C to 55°C
Temperature derating coefficient: not derated at 0°C–40°C,
derated to 0.9 at 41°C–45°C, derated to 0.8 at 46°C–50°C, and
derated to 0.7 at 51°C–55°C
Storage temperature
–40°C to +70°C
Relative humidity
0%–95% RH (non-condensing)
Altitude
0–1000 m
When the altitude is greater than 1000 m, the power is derated
as described in IEC 62040-3. The upper limit of the altitude is
4000 m.
Table 8-3
Safety compliance
Safety Certification
Standard