5 Operations
Issue 01 (2020-07-15)
Copyright © Huawei Technologies Co., Ltd.
137
After you set parameters on the
Settings Wizard
screen, choose
System Info
>
Settings
>
System
Settings
. Check that
Requisite modules
and
Redundant modules
match the actual values.
If dry contact signals are connected to the system, choose
System Info
>
Settings
>
Dry Contact
Set
. Check that the connected dry contacts have been enabled and that the disconnected dry contacts
have been disabled.
If the system has connected to the remote EPO switch, you need to choose
Monitoring
>
Param.
Settings
>
System Settings
on the WebUI and check that
EPO detection
is set to
Enable
.
Step 3
View the system running status diagram on the LCD to check that the UPS is working in
bypass mode.
----End
5.1.3 Starting the Inverter
UPS System User List
Table 5-1
UPS system user list
Default User
Preset Password
admin (administrator)
LCD
000001
Web
Changeme
operator (common user)
LCD
000001
Web
Changeme
browser (browsing user)
Web
-
Starting the Inverter on the LCD
Step 1
Choose
Common Functions
>
Inv. ON
.
You can also start the inverter by choosing
System Info
>
Maintenance
>
Inv. ON
.
Step 2
On the displayed login screen, select a user name and enter the password.
Step 3
In the displayed dialog box, tap
Yes
to start the inverter.
----End
Starting the Inverter on the WebUI
Step 1
Open a browser (Internet Explorer 11 as an example) and choose
Tools
>
Internet Options
.
Step 2
Click the
Advanced
tab, check that
Use TLS 1.0
and
Use TLS 1.1
are selected, and click
OK
.