4 Electrical Connection
Issue 04 (2018-04-10)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
59
Figure 4-16
Connecting the SmartLogger to a split EMI (1)
Step 1
Prepare a cable with an appropriate length, strip a proper part of the insulation layer from one
end, and connect the end to the port on the analog-to-digital converter.
The DJYP2VP2-22 2x2x1 computer cable or a communications cable with a conductor
cross-sectional area of 1 mm
2
and outer diameter of 14–18 mm is recommended.
For detailed operations, see the document delivered with the analog-to-digital converter.
Step 2
Connect the other end of the cable to the COM port of the SmartLogger. For details, see
Connecting Cables to the Terminal Block on the COM Port
When connecting cables, ensure that the RS485+ and RS485– ports on the analog-to-digital
converter respectively connect to the COM+ and COM– ports on the SmartLogger.
Step 3
The
Baud Rate
settings for the analog-to-digital converter and SmartLogger must be the
same.
For SmartLogger communication parameter settings, see
SUN2000 APP User Manual
.
For details about the communications parameter configurations for the analog-to-digital
converter, see the delivered document.
Step 4
Connect each sensor to the analog-to-digital converter. For detailed operations, see the
documents delivered with the analog-to-digital converter or sensors.
The EMI cannot be automatically identified. After connecting cables, log in to the embedded WebUI
and manually add the EMI. For details, see
. Set
Device Type
to
EMI
and
Connection mode
to
Modbus-RTU
.
After adding an EMI, set its parameters. For details, see
. The EMI model is
Sensor(ADAM)
.