168
If
Cubicle alarm enabling
is set to
Enable
, the
Abnormal Cubicle
alarm is generated when the dry
contact signal is effective and the Cubicle is abnormal.
7.10.7 Setting DI Parameters
You can set parameters for DI ports over the WebUI.
When a valid level is delivered into a DI port, an alarm is generated. You can set the
alarm name and severity.
A DI port shuts down the inverter using OVGR signals.
The SmartLogger provides eight DI ports, that is, DI1(GND1) to DI4(GND1) and DI5(GND2)
to DI8(GND2). For the connection method, see
4.10 Connecting a Ripple Control Receiver
Because of permission restriction, log in as
Special User
. Choose
Settings
>
DI
to access the
target page.
Figure 7-66
Setting DI parameters
If a DI port is activated, it cannot be set again under
Dry contact remote control
. If a DI port has been set in
Dry contact remote control
, it cannot be set here again.
Activation Status
: If the DI port is set to
Activated
, you can set the function of this DI
port. If the DI port is not set to
Activated
, you cannot set the function of this DI port.
Dry Contact Status
can be set to
Open
or
Close
. If
Activation Status
is set to
Activated
and
Dry Contact Status
is set to
Close
, it means that only when the DI port is
set to
Close
, the SmartLogger sends the inverter remote shutdown command.
If the SmartLogger connects to inverters over dry contacts and
Trigger Shutdown
is set
to
Enable
, the SmartLogger shuts down the inverters over OVGR signals.