Before manually adding a slave SmartLogger, set the Modbus TCP parameters correctly. Set
Link
setting
to
Enable
and enter the IP address of the slave SmartLogger in
Client IP address
. For
details, see
7.10.2.5 Setting Modbus TCP Parameters
. When adding the slave SmartLogger, set
Device Type
to
SmartLogger
and enter the IP address of the slave SmartLogger in
IP address
.
When connecting a third-party device, import a configuration file for the device, and then manually
add the device.
An accessed device can be removed manually, and a removed device can be added again.
Auto Assign Address
allows you to adjust device addresses based on serial numbers. If a device
cannot access due to address conflict, perform this operation to assign a new device address and then
access the device.
After the device is connected, you can export the device configuration. When changing the name of
the exported file, retain the extension
.cfg
. Otherwise, the file cannot be functional.
You can click the Start, Stop, or Reset icon to send the corresponding command to all inverters
connected to the SmartLogger. The login password is required if you need to send a command.
7.11.8.2 Device List
Because of permission restriction, log in as
Advanced User
or
Special User
. Choose
Maintenance
>
Device list
to access the target page.
Figure 7-79
Device list
You can modify the device name and address on the WebUI, or export a device information file in CSV
format and import the CSV file into the WebUI after modification.
7.11.8.3 Exporting Parameters
Because of permission restriction, log in as
Advanced User
or
Special User
. Choose
Maintenance
>
Export Param.
to access the target page.