8 Power Grid Scheduling
Issue 04 (2018-04-10)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
200
Figure 8-17
Power factor closed-loop control
Target power factor
: Sets the target value of the adjustment electricity meter power
factor.
Adjustment interval
: Sets the interval of sending adjustment commands by the
SmartLogger.
Adjustment deadband
: Sets the adjustment power factor precision.
The specified value of
Adjustment deadband
takes effect only if the electricity power factor exceeds
0.9.
8.3.10 Distributed Power Factor Closed-Loop Control
To improve the revenue, a distributed PV plant needs to reduce or avoid the power factor
surcharge by performing the distributed reactive power compensation. To enable the function,
set the related parameters over the WebUI.
Before setting the parameters, ensure that the power meter is connected to the SmartLogger.
For details, see
Set
Reactive power control mode
to
Distributed power factor closed-loop control
.