SmartLogger2000
User Manual
2 Product Overview
Issue 04 (2018-04-10)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
9
Bottom of the Shell
Figure 2-4
SmartLogger2000-10/10-B/11-B bottom
Table 2-2
Port description
No.
Port (Silk Screen)
Function
Description
1
RF1, RF2
Reserved
Reserved.
2
12V OUT
12 V DC output
Provides 12 V DC power supply with a
maximum current of 100 mA.
3
12V IN
12 V DC input
Connects to a power adapter.
4
USB
USB port
Connects to a USB flash drive.
5
SFP1, SFP2
Ethernet optical port
Connects to an Access Terminal Box
(ATB) or another cascaded SmartLogger.
6
ETH1, ETH2
Ethernet electrical port
Connects to an Ethernet switch, router,
POE module, or PC.
7
DO
Digital parameter output
Relay output; supports the voltage of 12 V
and current of 0.5 A.
8
COM1–COM6
RS485 communication
Six RS485 ports that can be connected to
devices such as the inverter, box-type
transformer, electricity meter, or EMI
9
Default
Default key
Resets and restarts the Bluetooth module
or resets the SmartLogger IP address to
the default IP address
a
. The default IP
address is 192.168.0.10.
10
AC1, AC2
AC power cable ports
SmartLogger2000-10/10-B: Connects
to the A, B, and C three-phase inputs,
and used for PLC with the SUN2000
over AC power cables. If PLC function
is not used, you do not have to connect
cables to these ports.
SmartLogger2000-11-B: disabled
11
External grounding
N/A