SmartLogger2000
User Manual
4 Electrical Connection
Issue 04 (2018-04-10)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
70
Follow-up Procedure
Disconnection can be performed in reverse order.
4.12 Connecting Fiber Jumpers
Context
The SmartLogger can be connected to devices such as an ATB through fiber jumpers. You can
select the devices to be connected based on the actual networking scenario. For details on
typical scenarios, see
2.4 Typical Networking Scenarios
Procedure
Step 1
Insert the optical module into
SFP1
or
SFP2
of the SmartLogger.
An optical module is optional. A 100M optical module (eSFP, 1310 nm, and single mode)
with transmission distance of at least 15 km is recommended.
When inserting an optical module into the
SFP1
port, verify that the side with a handle
faces upwards. When inserting an optical module into the
SFP2
port, verify that the side
with a handle faces downwards.
The optical switch used for the central control room supports RSTP and STP. To ensure the
communication between the optical switch and the SmartLogger, the configured optical
module must have a transmission speed of 100 Mbit/s.
Step 2
Connect the two fiber jumpers delivered with the optical module to the ports on the optical
module.
Step 3
Connect the other end of the fiber jumper to the port on the ATB.
Figure 4-28
Connecting an ATB