Indicator (Silk Screen)
Status
Meaning
Blinking green at short
intervals (0.125s on and
0.125s off)
Local maintenance fails.
----End
6.1.4 Upgrading the Application
Context
It is recommended that you use a SanDisk, Netac, or Kingston USB flash drive to ensure
compatibility.
The SmartLogger2000-10/10-B/11-B can only be upgraded by method 1.
The SmartLogger2000-10-C/11-C can be upgraded by method 1 or 2. Select either
method in practice.
Procedure
Method 1
a.
Log in to
http://support.huawei.com/carrier/
, browse or search for SmartLogger on
the
Product Support
tab page, and download the required upgrade package on the
Software
tab page.
The upgrade package is named
smartlogger2000.zip
. Store the upgrade package in the root directory of
a USB flash drive, and do not decompress it.
b.
Insert the USB flash drive into the USB port at the bottom of the SmartLogger.
c.
Log in to the app, choose
More
>
System Maintenance
>
Generate Local Maint.
Script
on the main menu page, and generate a boot script file. For details, see the
SUN2000 APP User Manual
.
d.
Replace the boot script file in the upgrade package with the boot script file in the
USB flash drive.
The boot script file in the upgrade package is named
logger_lmt_mgr_cmd.emap
.
e.
Insert the USB flash drive into the USB port at the bottom of the SmartLogger. The
SmartLogger automatically executes all commands specified in the boot script file.
View the LED indicator to determine the operating status.
Table 6-4
LED indicator description
Indicator (Silk Screen)
Status
Meaning
ALM
Green off
No local maintenance is in
progress.
Blinking green at long
intervals (1s on and 1s off)
Local maintenance is in
progress.