SmartLogger2000
User Manual
2 Product Overview
Issue 04 (2018-04-10)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
10
No.
Port (Silk Screen)
Function
Description
12
AI1–AI8
Analog input
SmartLogger2000-10: AI1–AI4
support 4–20 mA and 0–20 mA current
input (passive
b
); AI5–AI8 support
4–20 mA and 0–20 mA current input
(active
c
).
SmartLogger2000-10-B/11-B: AI1
supports 0–10 V voltage input
(passive); AI2–AI4 support 4–20 mA
and 0–20 mA current input (passive).
AI5–AI8 support 4–20 mA and 0–20
mA current input (active).
13
AO1–AO6
Analog output
4–20 mA and 0–20 mA current output
14
DI1–DI8
Digital parameter input
Connects to a dry contact input. GND1
and GND2 are grounding ports for DI
signals.
a:
If the APP fails to connect to the SmartLogger or you have forgotten the IP address, you can press the
Default key to reset the Bluetooth module or restore the IP address to the default IP address (192.168.0.10).
Press and hold down the Default key for 3s to 10s to reset and restart the Bluetooth module. Press and hold
down the Default key for 3s to 10s until the BLU indicator blinks at short intervals (on for 0.125s and then
off for 0.125s) and all the other indicators are off, and then release the Default key.
Press and hold down for more than 10s to restore the IP address to the default IP address. Press and hold
down the Default key for more than 10s until the RUN indicator blinks at short intervals (on for 0.125s and
then off for 0.125s) and all the other indicators are off, and then release the Default key. The operation is
valid within 5 minutes.
b: Passive means that the AI port supports the connection to a sensor that requires a separate external power
supply.
c: Active means that the AI port supports the connection to a sensor that does not require a separate external
power supply.
Figure 2-5
SmartLogger2000-10-C/11-C bottom