SmartLogger2000
User Manual
7 WebUI
Issue 04 (2018-04-10)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
104
No. Parameter
Description
Unit
Value Range
Remarks
8
Crystalline
silicon PV
compensation
mode
This parameter reduces
the DC voltage of PV
modules to the PE by
reducing the impedance of
the inverter input side to
the PE, thereby
effectively reducing PID
effect of PV modules.
N/A
Output
disabled
P-type
output
N-type
output
This parameter is displayed
if
PV module type
is set to
Crystalline silicon
. Set this
parameter to
P-type output
for P-type PV modules and
N-type output
for N-type
PV modules.
9
Communication
interrupt
shutdown
The standards of certain
countries and regions
require that the inverter
must shut down after the
communication is
interrupted for a certain
time.
N/A
Disable
Enable
If
Communication
interrupt shutdown
is set to
Enable
and the inverter
communication has been
interrupted for a specified
time (set by
Communication
interruption duration
), the
inverter will automatically
shut down.
10
Communication
interruption
duration
Specifies the duration for
determining
communication
interruption, and is used
for automatic shutdown
for protection in case of
communication
interruption.
min
[1, 120]
N/A
11
Communication
resumed startup
If this parameter is
enabled, the inverter
automatically starts after
communication recovers.
If this parameter is
disabled, the inverter
needs to be started
manually after
communication recovers.
N/A
Disable
Enable
This parameter is displayed
when
Communication
interrupt shutdown
is set to
Enable
.
12
Soft start time
Specifies the duration for
the power to gradually
increase when the inverter
starts.
s
[20, 1800]
This parameter is set to
360
by default if the Australian
AS4777 grid code is
selected, to
300
by default if
the Italian CEI0-21 or
CEI0-16 grid code is
selected, and to
600
by
default if the Egyptian
EGYPT grid code is
selected.
13
AFCI
The North American
standard requires the
inverter to provide the DC
arc detection function.
N/A
Disable
Enable
This parameter is supported
by the inverters named with
-US
.