171
Figure 7-69
Setting export limitation parameters
Parameter
Description
Parameter
Description
Power Meter
If
Export Limitation
is
set to
Enable
, set
Power
Meter
to
Smart meter
.
Otherwise the export
limitation would not take
effect.
Maximum protection
time
Setting the maximum
duration from the time
the SmartLogger detects
countercurrent to the time
it controls the inverter
output power to reach 0.
Suggestion: Set this
parameter based on the
maximum countercurrent
duration allowed by the
power grid company.
Electric meter power
direction
When the inverter does
not have output power,
set
Electric meter power
direction
to
Positive
if
the active power
displayed on the meter is
positive. Otherwise set it
to
Reverse
.
Power raising threshold
Setting the inverter
output power raising
threshold.
Maximum grid feed-in
power
Setting the maximum
power that the inverter
can transport to the power
grid.
Suggestion: Set this
parameter based on the
countercurrent threshold
allowed by the power
grid company.
Power limit for abnormal
electric meter
Setting the inverter
output power percentage
controlled by the
SmartLogger when
communication between
the SmartLogger and the
power meter is abnormal.