Alarm
ID
Alarm
Name
Alarm
Severity
Alarm
Sub-ID
Cause
Measures
1101
Abnorm
al
Q-Contr
ol
Major
4
Under the
reactive power
Dry contact
remote control
mode, the four
DI ports read
command
combinations
not configured.
1.
Verify that the cables are connected
correctly to the DI ports.
2.
Access the reactive power
Dry contact
remote control
configuration page and
check the mapping table of the DI signal
configuration. Contact the power grid
company and verify that the
combination configurations in the table
are complete and meet the requirements
of the company.
1103
Breaker
Disconn
ect
Major
1
The general
breaker at the
grid connection
point is
disconnected.
Check whether the disconnection is normal.
If it is abnormal, contact service engineers
to restore the breaker.
1104
Abnorm
al
Cubicle
Major
1
The Cubicle
device has
detected an
exception at the
grid connection
point.
When the Cubicle alarm is enabled, check
whether the DI signal received by the
SmartLogger is consistent with the dry
contact status. If so, restart the inverter.
1105
Device
Address
Conflict
Major
1
The
SmartLogger
RS485 address
conflicts with
the physical
address (RS485
address) or
logical address
for the
connected
southbound
device.
If the SmartLogger RS485 address
conflicts with the communication
address for the connected southbound
device, choose
Settings
>
Modbus TCP
and change the SmartLogger address, or
choose
Maintenance
>
Device
Mgmt.
>
Connect Device
and change
the southbound device address. If the
southbound device is a SUN2000, you
can change its address on the app.
If the SmartLogger RS485 address
conflicts with the logical address for the
connected southbound device, choose
Settings
>
Modbus TCP
and change
the SmartLogger address.
1106
AC SPD
fault
Major
1
The SPD in the
smart array
controller is
faulty.
Check whether the cable to the SPD in
the smart array controller is loose,
disconnected, or connected in reverse. If
so, reconnect the cable securely.
Check whether the SPD in the smart
array controller is faulty. Replace the
faulty SPD.