SmartLogger2000
User Manual
7 WebUI
Issue 04 (2018-04-10)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
112
No.
Parameter
Description
Unit
Value Range
Remarks
2
Phase
protection
point
The Japanese standard
requires that during
passive islanding
detection, protection
should be triggered if an
abrupt voltage phase
change is detected.
º
[3, 15]
Configurable
abruptly changed
phase angles are 3°,
6°, 9°, 12°, and 15°,
which are displayed
after the Japanese
grid code is
selected.
3
Phase angle
offset
protection
The standards of certain
countries and regions
require that the inverter
needs to be protected
when the three-phase
angle offset of the power
grid exceeds a certain
value.
N/A
Disable
Enable
N/A
4
10 minute
OV
protection
Specifies the 10-minute
overvoltage protection
threshold.
V
SUN2000-50KTL-M
0/60KTL-M0/65KTL
-C1/70KTL-C1/75KT
L-C1/70KTL-INM0:
[1xVn, 1.5xVn]
Others: [1xVn,
1.36xVn]
Vn represents the
rated voltage.
5
10 minute
OV
protection
time
Specifies the 10-minute
overvoltage protection
duration.
ms
1000 V inverter: [50,
600000]
Others: [50, 7200000]
6
Level-1 OV
protection
Specifies the level-1
overvoltage protection
threshold.
V
SUN2000-50KTL-M
0/60KTL-M0/65KTL
-C1/70KTL-C1/75KT
L-C1/70KTL-INM0:
[1xVn, 1.5xVn]
Others: [1xVn,
1.36xVn]
Vn represents the
rated voltage.
7
Level-1 OV
protection
time
Specifies the level-1
overvoltage protection
duration.
ms
1000 V inverter: [50,
600000]
Others: [50, 7200000]
8
Level-2 OV
protection
Specifies the level-2
overvoltage protection
threshold.
V
SUN2000-50KTL-M
0/60KTL-M0/65KTL
-C1/70KTL-C1/75KT
L-C1/70KTL-INM0:
[1xVn, 1.5xVn]
Others: [1xVn,
1.36xVn]
Vn represents the
rated voltage.