9 Device Maintenance
Issue 04 (2018-04-10)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
207
Alarm
ID
Alarm
Name
Alarm
Severity
Alarm
Sub-ID
Cause
Measures
1107–1
114
DI1
custom
alarm–D
I8
custom
alarm
Major
1
The dry contact
signal from the
peripheral to the
corresponding
DI port on the
SmartLogger is
abnormal.
Check the DI port cable connection. If
the cable is loose, disconnected, or
connected in reserve, reconnect it
securely.
Verify that the relevant device works
properly.
1115
24V
power
failure
Major
1
The 24 V power
module in the
smart array
controller is
faulty.
Check whether the cable to the 24 V
power module in the smart array
controller is loose, disconnected, or
connected in reverse. If so, reconnect
the cable securely.
Check whether the 24 V power module
in the smart array controller is faulty.
Replace the faulty power module.