SmartLogger2000
User Manual
7 WebUI
Issue 04 (2018-04-10)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
119
Power Adjustment Parameters
Table 7-9
Parameter description
No.
Parameter
Description
Unit
Value Range
Remarks
1
Active power
change
gradient
Adjusts the change speed
of the inverter active
power.
%/s
1000 V inverter:
[0.1, 50]
Others: [0.1,
1000]
N/A
2
Fixed active
power derated
Adjusts the active power
output of the inverter in
fixed values.
kW
1000 V inverter:
[0, Pmax]
Others: [0,
Pmax_limit]
Pmax represents
the maximum
active power.
For 1000 V
inverters, the
maximum value
of this parameter
for the
SUN2000-25KTL
-US is 27.5 kW.
This parameter is
for the
SUN2000-100KT
L-USH0 only and
displayed when
Remote power
schedule
is set to
Enable
.
3
Active power
percentage
derating
Adjusts the active power
output of the inverter in
percentages.
%
[0, 100]
If this parameter
is set to
100
, the
inverter delivers
the maximum
output power.
This parameter is
for the
SUN2000-100KT
L-USH0 only and
displayed when
Remote power
schedule
is set to
Enable
.
4
Reactive
power change
gradient
Adjusts the change speed
of the inverter reactive
power.
%/s
[0.1, 1000]
N/A