Location
Component
Recommended Model or
Specifications
Source of
Component
Quantity
MCCB
(solution 2)
When the rated AC voltage
on the low-voltage side of the
box-type transformer is less
than or equal to 500 V, the
rated voltage should be
greater than or equal to 500
V; when the rated AC voltage
on the low-voltage side of the
box-type transformer is
greater than 500 V and less
than or equal to 800 V, the
rated voltage should be
greater than or equal to 800 V
Let-through energy ≤ 1.26 x
10
6
A
2
s
Rated current: 32 A; number
of poles: 3
Prepared by
the customer
a: If the CPE is EG860 series, the POE and CPE fitting bags are configured with a POE SPD.