7 WebUI
Issue 04 (2018-04-10)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
103
No. Parameter
Description
Unit
Value Range
Remarks
4
Reactive power
output at night
In some specific
application scenarios, a
power grid company
requires that the inverter
can perform reactive
power compensation at
night to ensure that the
power factor of the local
power grid meets
requirements.
N/A
Disable
Enable
This parameter is available
only when
Isolation
is set to
Input ungrounded (with
TF)
.
5
Strong
adaptability
If the value of power grid
short circuit
capacity/power plant
installed capacity is less
than 3 and the power grid
impedance exceeds the
upper threshold, the
power grid quality will be
affected and the inverter
may be unable to run
properly. Set
Strong
adaptability
to
Enable
.
N/A
Disable
Enable
N/A
6
Power quality
optimization
mode
If
Power quality
optimization mode
is set
to
Enable
, the inverter
output current harmonics
will be optimized.
N/A
Disable
Enable
N/A
7
PV module type Specifies the type of PV
modules.
N/A
Crystalline
silicon
Film
CPV 1
CPV 2
If
PV module type
is set
to
Crystalline silicon
or
Film
, the inverter will
run properly and will not
shut down if PV modules
are shaded.
If
PV module type
is set
to
CPV 1
, the inverter
can restart quickly in 60
minutes if PV modules
are shaded and the input
power greatly decreases.
If
PV module type
is set
to
CPV 2
, the inverter
can restart quickly in 10
minutes if PV modules
are shaded and the input
power greatly decreases.