7 WebUI
Issue 04 (2018-04-10)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
179
Ensure that the extension of the license file to be imported is .dat or .zip.
7.11.8 Device Management
7.11.8.1 Connecting Devices
Because of permission restriction, log in as
Advanced User
or
Special User
. Choose
Maintenance
>
Connect Device
to access the target page.
Figure 7-78
Connecting devices
If the SmartLogger communicates with the inverter over PLC, set
Built-in PLC
to
Enable
after the
parameters are set. If the SmartLogger communicates with the inverter and third-party devices over
RS485 only, set
Built-in PLC
to
Disable
. For details, see
7.10.2.2 Setting RS485 Parameters
Huawei devices can be automatically recognized and connected or manually added. EMIs, electricity
meters, slave SmartLoggers, and third-party devices cannot be automatically recognized and must be
manually added.
If the devices connecting to different RS485 ports on the SmartLogger have address conflict (such as
COM1-1 and COM2-1), and the SmartLogger is communicating with a Huawei or third-party NMS,
set
Address mode
to
Logical address
7.10.2.4 Setting NetEco Parameters
7.10.2.5 Setting Modbus TCP Parameters
. If you do not set the parameter, ensure that the device
connecting to each RS485 port has a unique address.
Before manually adding an EMI connected over the COM port, set RS485 parameters correctly by
following the instructions in
7.10.2.2 Setting RS485 Parameters
. Then set
Device Type
to
EMI
and
Connection mode
to
Modbus-RTU
when adding the EMI. Before manually adding an EMI
connected over the AI/PT port, you do not have to set RS485 parameters. You only have to set
Device Type
to
EMI
and
Connection mode
to
AI
when adding the EMI. After adding an EMI
manually, correctly set the EMI parameters. For details, see
7.8.5.2 Setting Running Parameters
Before manually adding the Modbus or DL/T645 electricity meter, set RS485 parameters correctly
by following the instructions in
7.10.2.2 Setting RS485 Parameters
. Before manually adding the
Modbus electricity meter, correctly set the electricity meter parameters. For details, see
Setting Power Meter Parameters
. When adding an electricity meter, set
Device Type
to
Power
Meter
and
Comm.protocal
to the protocol supported by the electricity meter.