Solution
Recycle power to the module. If error persists, replace the module.
Check the Trace log for breadcrumbs that occurred prior to the event. Provide the results of the trace log
to Honeywell Solutions Support Center (SSC) for analysis.
Isolated (lonely) Node
For a redundant PGM pair, Fault Tolerant Ethernet (FTE) communications with partner and FTE network are
lost.
Diagnostic
Check
•
The primary module determines whether or not to initiate a switchover. If the secondary module
was known to be in a better condition than the primary at the time of fault determination, then the
primary should fail so the secondary will switchover. But, the new secondary (old primary) still
cannot restore FTE communications.
•
The secondary module should reboot once, in an attempt to restore communications. The primary
module will be able to report the problem in the secondary. If the secondary cannot restore FTE
communications, it should be able to resynchronize over the redundancy link and be a partially
functional backup.
Cause 1
Secondary module is defective.
Solution
Replace the secondary module that initiated switchover when fault was detected.
If secondary module synchronizes after replacement, the removed module is defective. Otherwise, go to
Cause 2.
Cause 2
Secondary IOTA is defective.
Solution
Replace the secondary IOTA that initiated switchover when fault was detected.
If secondary module synchronizes after replacement, the removed IOTA is defective. Otherwise, go to
Cause 3.
Cause 3
Primary module is defective.
Solution
Replace the primary module.
If you can command synchronization after replacement, the removed module is defective. Otherwise,
go to Cause 4.
Cause 4
Primary IOTA is defective.
Solution
Replace the primary IOTA.
If the module pair synchronize after IOTA replacement, the removed IOTA is defective. Otherwise, go
to Cause 5.
Cause 5
There is a software problem.
Solution
Contact Honeywell Solution Support Center (SSC).
Duplicate Device Index setting
The FTE subsystem detects duplicate Device Index settings in separate modules.
Diagnostic
Check
All modules will stop tracking cable status for the detected duplicate Device Index value.
Communications will continue and will not impact system performance until there is a cable fault. This
fault will also be detected by the FTE System Management Tool.
A duplicate Device Index could cause a duplicate IP Address. In most cases, the duplicate IP Address
would be detected first and prevent the FTE diagnostic messages from being sent.
Cause
Device Index switches on separate IOTA's are set to same value.
Solution
Change Device Index switches setting on one of the IOTA's to a unique value.
Device Index value is zero upon power up
The PGM's 4-character display shows a Device Index value of zero (#000).
13 PROFIBUS GATEWAY MODULE (PGM) TROUBLESHOOTING
260
www.honeywell.com
Содержание Experion PKS
Страница 1: ...Experion PKS PROFIBUS Gateway Module User s Guide EPDOC XX88 en 431E June 2018 Release 431 ...
Страница 8: ...CONTENTS 8 www honeywell com ...
Страница 10: ...1 ABOUT THIS GUIDE 10 www honeywell com ...
Страница 32: ...4 PROFIBUS GATEWAY MODULE PGM INSTALLATION 32 www honeywell com ...
Страница 58: ...5 PROFIBUS GATEWAY MODULE PGM BLOCK 58 www honeywell com ...
Страница 69: ...6 PROTOCOL BLOCK 69 ...
Страница 103: ...5 Click OK 6 PROTOCOL BLOCK 103 ...
Страница 109: ...You can modify the following value from the Protocol Main tab detail display Alarming Enabled 6 PROTOCOL BLOCK 109 ...
Страница 110: ...6 PROTOCOL BLOCK 110 www honeywell com ...
Страница 181: ...7 20 3 Detail display tab Main tab Figure 4 Detail Display of Main tab 7 DEVICE SUPPORT BLOCK DSB 181 ...
Страница 182: ...Slave Status tab Figure 5 Detail Display of Slave Status tab 7 DEVICE SUPPORT BLOCK DSB 182 www honeywell com ...
Страница 183: ...PDC Details tab Figure 6 Detail Display of PDC Details tab 7 DEVICE SUPPORT BLOCK DSB 183 ...
Страница 184: ...DPV1 Details tab Figure 7 Detail Display of DPV1 Details tab 7 DEVICE SUPPORT BLOCK DSB 184 www honeywell com ...
Страница 185: ...Config Details tab Figure 8 Detail Display of Config Details tab 7 DEVICE SUPPORT BLOCK DSB 185 ...
Страница 186: ...7 DEVICE SUPPORT BLOCK DSB 186 www honeywell com ...
Страница 229: ...For a digital channel the detail display appears as follows 9 PROFIBUS I O MODULE PIOMB FUNCTION BLOCK 229 ...
Страница 231: ...9 PROFIBUS I O MODULE PIOMB FUNCTION BLOCK 231 ...
Страница 232: ...9 PROFIBUS I O MODULE PIOMB FUNCTION BLOCK 232 www honeywell com ...
Страница 236: ...10 PROFIBUS GATEWAY MODULE PGM CONFIGURATION EXAMPLE 236 www honeywell com ...
Страница 264: ...13 PROFIBUS GATEWAY MODULE PGM TROUBLESHOOTING 264 www honeywell com ...