PGM does not synchronize with backup
Diagnostic Check
Primary module cannot synchronize with secondary module.
In the Monitoring view, double-click the primary PGM icon to display the block configuration form.
Click the
Redundancy
tab and check the Inhibit Sync Reason parameter description for not achieving
synchronization.
Troubleshoot to correct condition for inhibiting sync.
Cause 1
Redundancy cable bad.
Solution
Replace redundancy cable. Check if the modules synchronize.
Cause 2
PBLink cables may be disconnected.
Solution
Reconnect cables to the PGM IOTA.
Cause 3
Secondary module bad.
Solution
Replace the module. Check if the modules synchronize.
Cause 4
Backup IOTA bad.
Solution
Replace the IOTA. Reinstall the original secondary module on the new IOTA. Check if modules
synchronize.
Cause 5
Primary module bad.
Solution
Replace primary IOTA. Reinstall the original primary module on the new IOTA. Check if modules
synchronize.
Cause 6
Software problem.
Solution
Contact Honeywell SSC.
Fatal ECC error
The PGM software has detected a fatal Error Checking and Correction (ECC) condition that can be a multiple-
bit error or excessive single-bit errors in the main Random Access Memory (RAM).
Diagnostic
Check
•
The 4-character display on the modules displays FAIL or mMBE.
•
In the Monitoring view, the PGM icon turns red.
Cause
The PGM software has detected a failure that does not allow operation to continue. There can be many
causes for a failure including hardware.
Use the CTools utility to capture diagnostic data for the device to determine the possible cause before
proceeding. If the error occurs in the backup RAM, a fault is indicated. If the error occurs in main RAM,
the module freezes with mMBE on the display.
Solution
Try shorting the reset pads on the IOTA to restart the module. If error persists, replace the module.
Check the Trace log for breadcrumbs that occurred prior to the event. Provide the results of the trace log to
Honeywell Solutions Support Center (SSC) for analysis.
Display shows FAIL
The PGM detects failure during system integrity checks, such as Watch Dog Timer (WDT), error detection
circuits, microprocessor static configuration registers, and Read Only Memory (ROM) checksum.
Diagnostic
Check
•
The 4-character display on the PGM displays FAIL.
•
In the Monitoring view, the PGM icon turns red.
Cause
The PGM software has detected a background diagnostic failure that does not allow operation to
continue.
13 PROFIBUS GATEWAY MODULE (PGM) TROUBLESHOOTING
259
Содержание Experion PKS
Страница 1: ...Experion PKS PROFIBUS Gateway Module User s Guide EPDOC XX88 en 431E June 2018 Release 431 ...
Страница 8: ...CONTENTS 8 www honeywell com ...
Страница 10: ...1 ABOUT THIS GUIDE 10 www honeywell com ...
Страница 32: ...4 PROFIBUS GATEWAY MODULE PGM INSTALLATION 32 www honeywell com ...
Страница 58: ...5 PROFIBUS GATEWAY MODULE PGM BLOCK 58 www honeywell com ...
Страница 69: ...6 PROTOCOL BLOCK 69 ...
Страница 103: ...5 Click OK 6 PROTOCOL BLOCK 103 ...
Страница 109: ...You can modify the following value from the Protocol Main tab detail display Alarming Enabled 6 PROTOCOL BLOCK 109 ...
Страница 110: ...6 PROTOCOL BLOCK 110 www honeywell com ...
Страница 181: ...7 20 3 Detail display tab Main tab Figure 4 Detail Display of Main tab 7 DEVICE SUPPORT BLOCK DSB 181 ...
Страница 182: ...Slave Status tab Figure 5 Detail Display of Slave Status tab 7 DEVICE SUPPORT BLOCK DSB 182 www honeywell com ...
Страница 183: ...PDC Details tab Figure 6 Detail Display of PDC Details tab 7 DEVICE SUPPORT BLOCK DSB 183 ...
Страница 184: ...DPV1 Details tab Figure 7 Detail Display of DPV1 Details tab 7 DEVICE SUPPORT BLOCK DSB 184 www honeywell com ...
Страница 185: ...Config Details tab Figure 8 Detail Display of Config Details tab 7 DEVICE SUPPORT BLOCK DSB 185 ...
Страница 186: ...7 DEVICE SUPPORT BLOCK DSB 186 www honeywell com ...
Страница 229: ...For a digital channel the detail display appears as follows 9 PROFIBUS I O MODULE PIOMB FUNCTION BLOCK 229 ...
Страница 231: ...9 PROFIBUS I O MODULE PIOMB FUNCTION BLOCK 231 ...
Страница 232: ...9 PROFIBUS I O MODULE PIOMB FUNCTION BLOCK 232 www honeywell com ...
Страница 236: ...10 PROFIBUS GATEWAY MODULE PGM CONFIGURATION EXAMPLE 236 www honeywell com ...
Страница 264: ...13 PROFIBUS GATEWAY MODULE PGM TROUBLESHOOTING 264 www honeywell com ...