• The DSB communicates with the slave devices through this address. The slave device address must be
unique for a Protocol Block.
Attention
•
For GENPADSB, the transparent segment coupler displays all devices connected to the PROFIBUS PA
network as if they were PROFIBUS DP field devices.
•
For GENPAGWDSB, the PROFIBUS DP/PA link, Siemens DP/PA link IM-157, is a DP slave that acts as a
proxy for the PA field devices. The DP/PA Link reserves one PROFIBUS DP slave address.
11
In the
Device Type
box, type the description of the device type.
12
In the
Connection Break TimeOut (Sec)
box, type the duration in seconds during which the network
communication break needs to be filtered off.
If the communication break condition persists even after this time, then the status of the slave device is set to
“
Communication Error
.” This parameter is applicable only when the slave device is disconnected from the
Profibus network. If the complete Profibus network is down, the status of all slave devices is set to
“
Communication Error
” immediately.
13
Select the
Connection Break Timeout applicable for Network Down
check box if you want the output
channels to initialize back from the user-defined values after the connection break timeout timer is exceeded.
If the complete Profibus network is down and you have not selected this check box, the status of all slave
devices is set to “
Communication Error
” immediately.
However, if you have selected this check box and the complete Profibus network is down, the status of all
slave devices are set to “
Communication Error
” after the connection break timeout is exceeded.
14
Select the
Reset counters
check box if you want to reset all static counters.
15
Click the
Slave Status
tab.
Attention
The
Slave Status
tab displays the slave communication standard status bits and extended diagnostic information in
the Monitoring view. .
16
Click the
Alarms
tab.
The
Alarms
tab is only applicable to the Generic DSBs and the DRIVEDSB as you can configure alarms
only for these DSBs.
17
Click the
PDC
tab.
Attention
The
PDC
tab of the DSB block is used for defining the PDCs. You cannot proceed with the DSB configuration
until you complete the PDC configuration. To configure the PDCs, see section Configuring the PDC tab.
18
Use the online help as a guide to complete the configuration entries on all other tabs.
19
Click
OK
.
7 DEVICE SUPPORT BLOCK (DSB)
149
Содержание Experion PKS
Страница 1: ...Experion PKS PROFIBUS Gateway Module User s Guide EPDOC XX88 en 431E June 2018 Release 431 ...
Страница 8: ...CONTENTS 8 www honeywell com ...
Страница 10: ...1 ABOUT THIS GUIDE 10 www honeywell com ...
Страница 32: ...4 PROFIBUS GATEWAY MODULE PGM INSTALLATION 32 www honeywell com ...
Страница 58: ...5 PROFIBUS GATEWAY MODULE PGM BLOCK 58 www honeywell com ...
Страница 69: ...6 PROTOCOL BLOCK 69 ...
Страница 103: ...5 Click OK 6 PROTOCOL BLOCK 103 ...
Страница 109: ...You can modify the following value from the Protocol Main tab detail display Alarming Enabled 6 PROTOCOL BLOCK 109 ...
Страница 110: ...6 PROTOCOL BLOCK 110 www honeywell com ...
Страница 181: ...7 20 3 Detail display tab Main tab Figure 4 Detail Display of Main tab 7 DEVICE SUPPORT BLOCK DSB 181 ...
Страница 182: ...Slave Status tab Figure 5 Detail Display of Slave Status tab 7 DEVICE SUPPORT BLOCK DSB 182 www honeywell com ...
Страница 183: ...PDC Details tab Figure 6 Detail Display of PDC Details tab 7 DEVICE SUPPORT BLOCK DSB 183 ...
Страница 184: ...DPV1 Details tab Figure 7 Detail Display of DPV1 Details tab 7 DEVICE SUPPORT BLOCK DSB 184 www honeywell com ...
Страница 185: ...Config Details tab Figure 8 Detail Display of Config Details tab 7 DEVICE SUPPORT BLOCK DSB 185 ...
Страница 186: ...7 DEVICE SUPPORT BLOCK DSB 186 www honeywell com ...
Страница 229: ...For a digital channel the detail display appears as follows 9 PROFIBUS I O MODULE PIOMB FUNCTION BLOCK 229 ...
Страница 231: ...9 PROFIBUS I O MODULE PIOMB FUNCTION BLOCK 231 ...
Страница 232: ...9 PROFIBUS I O MODULE PIOMB FUNCTION BLOCK 232 www honeywell com ...
Страница 236: ...10 PROFIBUS GATEWAY MODULE PGM CONFIGURATION EXAMPLE 236 www honeywell com ...
Страница 264: ...13 PROFIBUS GATEWAY MODULE PGM TROUBLESHOOTING 264 www honeywell com ...