Loss of power
The power supply has failed or the main power source has been shutdown or is experiencing a brownout or
blackout condition.
Diagnostic Check
•
The 4-character display on the PGM and LEDs on the module and the IOTA are off.
•
In the Monitoring view, the PGM icon turns red.
Cause 1
Main power source has been disconnected or shutdown either manually or temporarily by brownout or
blackout condition.
Solution
Re-connect the main power source or turn it On or wait for temporary brownout or blackout condition
to pass.
Cause 2
The 24 Vdc power supply failed or power cable has been disconnected or failed.
Solution
Replace the 24 Vdc power supply or re-connect/replace the power cable.
Cause 3
Power fuse opens on IOTA.
Solution
Replace power fuse.
Power-On Self Test (POST) does not complete
A fault is detected during the Power-On Self Test (POST).
Diagnostic
Check
A self test diagnostic code remains on display and the POST does not continue.
Possible indications: Display indicates test pattern, or Tnnn (nnn = a test number which is executed
during POST). Note: If display indicates 'T499', POST has completed.
Cause
The PGM POST has detected a failure that does not allow startup to continue or complete.
Solution
Short the reset pads on the IOTA to restart the PGM. If error persists, replace the module.
PGM display indicates -bp- or -ts-
Diagnostic Check
Display indicates -bp-
Cause
BootP service is not available.
Solution
•
Check FTE cable connections to FTE A and FTE B
connectors on the module IOTA.
•
Verify FTE network connections between the module
IOTA and the associated server.
•
Verify that the BootP service is running on the associated
server. Restart BootP service if not running.
•
In Control Builder, check System Preferences for valid
network IP address settings. Verify correct configuration
of System Time server.
Diagnostic
Check
Display indicates -SF- alternating with OK/BKUP
Cause
BootP service is available, but time source is not available. Time Server may not be configured or
server may not be running the latest release time service.
Solution
Verify that the system time source is configured. Check that the Server Windows Time Service
(w32time) is running on the server.
One or both FTE LEDs are RED
Diagnostic Check
One or both FTE LEDs on the PGM faceplate are RED.
13 PROFIBUS GATEWAY MODULE (PGM) TROUBLESHOOTING
257
Содержание Experion PKS
Страница 1: ...Experion PKS PROFIBUS Gateway Module User s Guide EPDOC XX88 en 431E June 2018 Release 431 ...
Страница 8: ...CONTENTS 8 www honeywell com ...
Страница 10: ...1 ABOUT THIS GUIDE 10 www honeywell com ...
Страница 32: ...4 PROFIBUS GATEWAY MODULE PGM INSTALLATION 32 www honeywell com ...
Страница 58: ...5 PROFIBUS GATEWAY MODULE PGM BLOCK 58 www honeywell com ...
Страница 69: ...6 PROTOCOL BLOCK 69 ...
Страница 103: ...5 Click OK 6 PROTOCOL BLOCK 103 ...
Страница 109: ...You can modify the following value from the Protocol Main tab detail display Alarming Enabled 6 PROTOCOL BLOCK 109 ...
Страница 110: ...6 PROTOCOL BLOCK 110 www honeywell com ...
Страница 181: ...7 20 3 Detail display tab Main tab Figure 4 Detail Display of Main tab 7 DEVICE SUPPORT BLOCK DSB 181 ...
Страница 182: ...Slave Status tab Figure 5 Detail Display of Slave Status tab 7 DEVICE SUPPORT BLOCK DSB 182 www honeywell com ...
Страница 183: ...PDC Details tab Figure 6 Detail Display of PDC Details tab 7 DEVICE SUPPORT BLOCK DSB 183 ...
Страница 184: ...DPV1 Details tab Figure 7 Detail Display of DPV1 Details tab 7 DEVICE SUPPORT BLOCK DSB 184 www honeywell com ...
Страница 185: ...Config Details tab Figure 8 Detail Display of Config Details tab 7 DEVICE SUPPORT BLOCK DSB 185 ...
Страница 186: ...7 DEVICE SUPPORT BLOCK DSB 186 www honeywell com ...
Страница 229: ...For a digital channel the detail display appears as follows 9 PROFIBUS I O MODULE PIOMB FUNCTION BLOCK 229 ...
Страница 231: ...9 PROFIBUS I O MODULE PIOMB FUNCTION BLOCK 231 ...
Страница 232: ...9 PROFIBUS I O MODULE PIOMB FUNCTION BLOCK 232 www honeywell com ...
Страница 236: ...10 PROFIBUS GATEWAY MODULE PGM CONFIGURATION EXAMPLE 236 www honeywell com ...
Страница 264: ...13 PROFIBUS GATEWAY MODULE PGM TROUBLESHOOTING 264 www honeywell com ...