• Number of Channels (NUMCHANS)
• Channel Number Offset (CHANNUMOFFSET)
• PDC Grouped (GROUPEDPDC)
For example, consider that two analog input modules are grouped and the slot 1 belongs to analog input
module 1 and slot 2 belongs to analog input module 2.
The
PDC Grouped (GROUPEDPDC)
parameter is indicated as “GREEN,” and the
Number of channels
(NUMCHANS)
parameter can be modified.
8
Type the physical slot number of the PBHIOMB in the
Slot Number (SLOTNUM)
box.
Attention
If the
Slot Type (SLOTTYPE)
parameter is displayed as “Analog output (AO),” then AO channel value must be
manually set as equal to or greater than 3.6 mA for establishing the HART communication for AO devices.
9
In the
Number of Channels (NUMCHANS)
box, type the number of channels to be associated with the
PBHIOMB.
If you want to configure the PBHIOMB for slot 1, then type the slot number in the
SLOTNUM
box and
then type the number of channels in the
NUMCHANS
box.
10
In the
HART Configuration
tab, perform the following steps.
a
Type the process data index in the
Directory Process Data Index (DIRPROCDATAINDEX)
box.
Note
Directory Process Data Index (DIRPROCDATAINDEX)
value must be taken from the device manual.
See the specific device manuals for the data. The
DIRPROCDATAINDEX
value can also obtained from
the GSD file
b
Select the check boxes for the respective HART Enabled channels.
The channel name is automatically displayed in the
Channel Name (CHNLNAME)
column.
Note
The
Channel Name (CHNLNAME)
can be edited only in the Project view.
11
Click
OK
.
The HART Enabled channels appear under the PBHIOMB block in the Project view.
To configure a PBHIOMB block for Universal Modules
1
Click
File
>
New
>
I/O Modules
>
PGM_IF
> PBHIOMB.
When you create a PBHIOMB, it resides in the
Unassigned
folder in the Project tree. You must drag-and-
drop it to the DSB.
2
(Optional) Perform the following steps.
a
Drag-and-drop the PBHIOMB from the PGM_IF library to the DSB that is assigned to a PBLINK.
The
Name New Function Blocks
dialog box appears.
b
In the
Destination
column, you can accept the default name or modify the name, if required and then
click
Finish
.
The PBHIOMB block appears under the DSB block.
3
Double-click the PBHIOMB.
The PBHIOMB block configuration form appears.
4
In the
Tag Name
box, type the name of the PBHIOMB (a maximum of 16 characters) or accept the default.
5
In the
Item Name
box, type the item name.
6
In the
Description (DESC)
box, type a brief description of up to 132 characters.
7
Click the point picker to configure the
PDC Name Reference (PDCNAMEREF)
and then select the
associated HART-enabled device in which the PDC is grouped.
8 PROFIBUS HART INPUT/OUTPUT MODULE (PBHIOM) FUNCTION BLOCK
195
Содержание Experion PKS
Страница 1: ...Experion PKS PROFIBUS Gateway Module User s Guide EPDOC XX88 en 431E June 2018 Release 431 ...
Страница 8: ...CONTENTS 8 www honeywell com ...
Страница 10: ...1 ABOUT THIS GUIDE 10 www honeywell com ...
Страница 32: ...4 PROFIBUS GATEWAY MODULE PGM INSTALLATION 32 www honeywell com ...
Страница 58: ...5 PROFIBUS GATEWAY MODULE PGM BLOCK 58 www honeywell com ...
Страница 69: ...6 PROTOCOL BLOCK 69 ...
Страница 103: ...5 Click OK 6 PROTOCOL BLOCK 103 ...
Страница 109: ...You can modify the following value from the Protocol Main tab detail display Alarming Enabled 6 PROTOCOL BLOCK 109 ...
Страница 110: ...6 PROTOCOL BLOCK 110 www honeywell com ...
Страница 181: ...7 20 3 Detail display tab Main tab Figure 4 Detail Display of Main tab 7 DEVICE SUPPORT BLOCK DSB 181 ...
Страница 182: ...Slave Status tab Figure 5 Detail Display of Slave Status tab 7 DEVICE SUPPORT BLOCK DSB 182 www honeywell com ...
Страница 183: ...PDC Details tab Figure 6 Detail Display of PDC Details tab 7 DEVICE SUPPORT BLOCK DSB 183 ...
Страница 184: ...DPV1 Details tab Figure 7 Detail Display of DPV1 Details tab 7 DEVICE SUPPORT BLOCK DSB 184 www honeywell com ...
Страница 185: ...Config Details tab Figure 8 Detail Display of Config Details tab 7 DEVICE SUPPORT BLOCK DSB 185 ...
Страница 186: ...7 DEVICE SUPPORT BLOCK DSB 186 www honeywell com ...
Страница 229: ...For a digital channel the detail display appears as follows 9 PROFIBUS I O MODULE PIOMB FUNCTION BLOCK 229 ...
Страница 231: ...9 PROFIBUS I O MODULE PIOMB FUNCTION BLOCK 231 ...
Страница 232: ...9 PROFIBUS I O MODULE PIOMB FUNCTION BLOCK 232 www honeywell com ...
Страница 236: ...10 PROFIBUS GATEWAY MODULE PGM CONFIGURATION EXAMPLE 236 www honeywell com ...
Страница 264: ...13 PROFIBUS GATEWAY MODULE PGM TROUBLESHOOTING 264 www honeywell com ...