7.16 Configuring the PDC
The
PDC
tab of the DSB block is used to define the PDCs. The slave device data is accessed through the
configuration in the PDC tab. The PDC tab is divided into upper and lower grid. The upper grid is used to
configure the module types. The lower grid displays the channels and the channel-related information of the I/O
modules selected in the upper grid.
Attention
•
You can use the following procedure for configuring parameters that are generic to all DSBs. However, you must
refer to the <DSB name> specific PDC configuration guidelines section for information on DSB specific
parameters. For example, for Generic DSB specific PDC configuration, you can refer to the section “Generic DSB
specific PDC configuration guidelines.”
•
For Turck Excom DSB and Siemens ET200M DSB, the PDC configuration must be done through IOM
configuration tab.
Perform the following steps to configure the PDC
1
Click the
PDC
tab in the DSB block configuration form.
The PDC tab configuration form appears.
2
In the
PDC Type
list, select the appropriate I/O module.
This list represents the module types supported by the DSB. The PDC types that appear in this list may vary
based on the DSB that is selected.
When you select a specific PDC type in the upper grid, all the channel information and the channel
parameters of the configured I/O modules appear in the lower grid.
Attention
After the PDC is associated with a PIOMB, you cannot modify the PDC type.
3
In the
PDC Description
column, type a description for the PDC.
The description you provide here can be used to identify the correct PDC when associating the PDCs to the
PIOMB.
4
In the
Net Tag Name
column, select the correct net tag name against the PDC type.
The tag names that appear in this list are the names that you have defined while configuring the slave device
in the “Profibus Network Configuration Tool”. The net tag name is unique for each I/O module. You cannot
select the same net tag name for two I/O modules inside a slave device. However, you can use the same net
tag name for another slave device.
5
Select the
Hold on failure
check box if you want the DSB to hold the last output value in the event of a
communication error between the C300 and the PGM.
6
In the
Number of Channels
column, type the number of channels that the PDC supports.
By default, the number of channels is set to "1."
7
In the
Channel Description
column, type a brief description (maximum of 32 characters) of the channel.
8
In the
Channel Type
column, select the type of the channel.
• The channel types can be Digital Input, Digital Output, Analog Input, and Analog Output.
• The values that appear in this list may vary based on the DSB selected.
• If you have used the fixed PDC types, the channel types are displayed automatically.
• You must define the channel type if you have used the configurable input/output PDCs.
9
In the
Channel Data Type
column, select the data type of the channel.
• The channel data types can be Boolean, Uint8, Uint16, Uint32, Int8, Int16, Int32, and Float32. The
values that appear in this list may vary based on the DSB selected.
• If you have used the fixed PDC types, the channel data types are displayed automatically.
7 DEVICE SUPPORT BLOCK (DSB)
156
www.honeywell.com
Содержание Experion PKS
Страница 1: ...Experion PKS PROFIBUS Gateway Module User s Guide EPDOC XX88 en 431E June 2018 Release 431 ...
Страница 8: ...CONTENTS 8 www honeywell com ...
Страница 10: ...1 ABOUT THIS GUIDE 10 www honeywell com ...
Страница 32: ...4 PROFIBUS GATEWAY MODULE PGM INSTALLATION 32 www honeywell com ...
Страница 58: ...5 PROFIBUS GATEWAY MODULE PGM BLOCK 58 www honeywell com ...
Страница 69: ...6 PROTOCOL BLOCK 69 ...
Страница 103: ...5 Click OK 6 PROTOCOL BLOCK 103 ...
Страница 109: ...You can modify the following value from the Protocol Main tab detail display Alarming Enabled 6 PROTOCOL BLOCK 109 ...
Страница 110: ...6 PROTOCOL BLOCK 110 www honeywell com ...
Страница 181: ...7 20 3 Detail display tab Main tab Figure 4 Detail Display of Main tab 7 DEVICE SUPPORT BLOCK DSB 181 ...
Страница 182: ...Slave Status tab Figure 5 Detail Display of Slave Status tab 7 DEVICE SUPPORT BLOCK DSB 182 www honeywell com ...
Страница 183: ...PDC Details tab Figure 6 Detail Display of PDC Details tab 7 DEVICE SUPPORT BLOCK DSB 183 ...
Страница 184: ...DPV1 Details tab Figure 7 Detail Display of DPV1 Details tab 7 DEVICE SUPPORT BLOCK DSB 184 www honeywell com ...
Страница 185: ...Config Details tab Figure 8 Detail Display of Config Details tab 7 DEVICE SUPPORT BLOCK DSB 185 ...
Страница 186: ...7 DEVICE SUPPORT BLOCK DSB 186 www honeywell com ...
Страница 229: ...For a digital channel the detail display appears as follows 9 PROFIBUS I O MODULE PIOMB FUNCTION BLOCK 229 ...
Страница 231: ...9 PROFIBUS I O MODULE PIOMB FUNCTION BLOCK 231 ...
Страница 232: ...9 PROFIBUS I O MODULE PIOMB FUNCTION BLOCK 232 www honeywell com ...
Страница 236: ...10 PROFIBUS GATEWAY MODULE PGM CONFIGURATION EXAMPLE 236 www honeywell com ...
Страница 264: ...13 PROFIBUS GATEWAY MODULE PGM TROUBLESHOOTING 264 www honeywell com ...