7.19 Setting the channel output values from Monitoring view
If you have not associated a PDC to a PIOMB block, you can set the analog or digital channel output values
from the Monitoring view.
Attention
You cannot set the channel input values from the Monitoring view. An error message appears when you try to set the
channel input values from the Monitoring view.
Related topics
“Setting the analog output values” on page 178
“Setting the digital output values” on page 178
7.19.1 Setting the analog output values
Perform the following steps to set the analog output values
1
Select the PDC type from the
PDC
tab. All the channels of the specific PDC type are listed in the lower
grid.
2
Click the floating point value or the numeric raw data value of the channel for which you want to modify the
value. A confirmation message appears.
3
Click
Yes
.
Attention
If the PDC is associated with a PIOMB, you cannot modify the output values. An error message appears if you try
to modify the output value.
4
Type the new value in the
Numeric raw data
column or the
Floating point value
column.
Attention
•
You must enter the raw value in the
Numeric raw data
column and the percentage in the
Floating point
value
column.
•
When you enter the numeric raw value in the
Numeric raw data
column, the floating point value must appear
automatically in the
Floating point value
column. Similarly, when you enter the floating point value in the
Floating point value
column, the numeric raw data must automatically appear in the
Numeric raw data
column.
For example, for a 0 to 20 mA signal, if the channel high range is 20000 and the channel low range is 0, if you
enter the floating point value as 50%, the
Numeric raw data
column will display the value as 10000.
•
If you enter a value that exceeds the extended range value, the message "kVAStsLimitOrRangeExceeded"
appears and the last good value is retained.
•
In a CEAGDSB, you cannot change the channel values of the PDCs associated with the CEAG
Communication module.
5
Click
OK
.
7.19.2 Setting the digital output values
Perform the following steps to set the digital output values
1
Select the PDC type from the PDC tab.
All the channels of the specific PDC type are listed in the lower grid.
2
Clear or select the check box depending on whether the output value needs to be ON or OFF. A confirmation
message appears.
7 DEVICE SUPPORT BLOCK (DSB)
178
www.honeywell.com
Содержание Experion PKS
Страница 1: ...Experion PKS PROFIBUS Gateway Module User s Guide EPDOC XX88 en 431E June 2018 Release 431 ...
Страница 8: ...CONTENTS 8 www honeywell com ...
Страница 10: ...1 ABOUT THIS GUIDE 10 www honeywell com ...
Страница 32: ...4 PROFIBUS GATEWAY MODULE PGM INSTALLATION 32 www honeywell com ...
Страница 58: ...5 PROFIBUS GATEWAY MODULE PGM BLOCK 58 www honeywell com ...
Страница 69: ...6 PROTOCOL BLOCK 69 ...
Страница 103: ...5 Click OK 6 PROTOCOL BLOCK 103 ...
Страница 109: ...You can modify the following value from the Protocol Main tab detail display Alarming Enabled 6 PROTOCOL BLOCK 109 ...
Страница 110: ...6 PROTOCOL BLOCK 110 www honeywell com ...
Страница 181: ...7 20 3 Detail display tab Main tab Figure 4 Detail Display of Main tab 7 DEVICE SUPPORT BLOCK DSB 181 ...
Страница 182: ...Slave Status tab Figure 5 Detail Display of Slave Status tab 7 DEVICE SUPPORT BLOCK DSB 182 www honeywell com ...
Страница 183: ...PDC Details tab Figure 6 Detail Display of PDC Details tab 7 DEVICE SUPPORT BLOCK DSB 183 ...
Страница 184: ...DPV1 Details tab Figure 7 Detail Display of DPV1 Details tab 7 DEVICE SUPPORT BLOCK DSB 184 www honeywell com ...
Страница 185: ...Config Details tab Figure 8 Detail Display of Config Details tab 7 DEVICE SUPPORT BLOCK DSB 185 ...
Страница 186: ...7 DEVICE SUPPORT BLOCK DSB 186 www honeywell com ...
Страница 229: ...For a digital channel the detail display appears as follows 9 PROFIBUS I O MODULE PIOMB FUNCTION BLOCK 229 ...
Страница 231: ...9 PROFIBUS I O MODULE PIOMB FUNCTION BLOCK 231 ...
Страница 232: ...9 PROFIBUS I O MODULE PIOMB FUNCTION BLOCK 232 www honeywell com ...
Страница 236: ...10 PROFIBUS GATEWAY MODULE PGM CONFIGURATION EXAMPLE 236 www honeywell com ...
Страница 264: ...13 PROFIBUS GATEWAY MODULE PGM TROUBLESHOOTING 264 www honeywell com ...