13
Click
Apply
.
14
Click
OK
.
15
Click
Save
on the
Field Network Configuration
tab toolbar.
Attention
When you click
Save
, the configuration is saved temporarily.
16
Double-click the master (PROFIBUS Gateway) in the Network view.
The configuration window appears. The
Device Assignment
menu in the
Navigation Area
is selected by
default.
17
Click the
Process Data
menu in the
Navigation Area
.
The process data of the ET 200M(IM153-1) device appear in the right pane.
18
Click
to view the input and output modules that are assigned to the ET 200M(IM153-1) device.
19
Select the Input_1 tag in the
Tag
column and modify it as Input_1_Exm.
20
Select the Output_1 tag in the
Tag
column and modify it as Output_1_Exm.
21
Click
Apply
.
22
Drag-and-drop the GENDSB from the DSB library to the PBLINK_2230.
The
Load Dialog
box appears.
23
Click
OK
.
24
Double-click the GENDSB.
25
Type the name of the DSB (a maximum of 16 characters) or accept the default.
26
Click
OK
.
27
Click the
PDC
tab.
28
Select the Digital inputs ch 0-31 and Digital outputs ch 0-31 from the
PDC Type
list.
29
Type the description for the Digital inputs ch 0-31 PDC as "Digital input channel" in the
PDC Description
column.
30
Type the description for the Digital output ch 0-31 PDC as "Digital output channel" in the
PDC Description
column.
31
Select the tag Input_1_Exm for the input PDC and Output_1_Exm for the output PDC type in the
Net Tag
Name
column respectively.
When you select the Digital inputs ch 0-31 or the Digital output ch 0-31 row, the lower grid will display 4
rows (one row for each column) with all the channel information.
32
Enter 4 in the
Number of Channels
column for both the input and output types.
33
Click
OK
.
34
Drag-and-drop the PIOMB block from the PGM_IF library to the CEE of the C300 Controller.
35
Double-click the PIOMB (PIOMB_2239).
36
Click the point picker button next to the
PDC Name Reference
box.
The
Point Selection
dialog box appears.
37
Choose the PDC with the PDC description as "Digital input channel" to be associated to the PIOMB.
38
Repeat step 34 through step 37 to associate a PDC with the PDC description "Digital output channel" to
another PIOMB.
39
Click
OK
.
The
PDC Name Reference
field will display the PDC name that is associated to the PIOMB in the Main tab
of the PIOMB block.
40
Drag-and-drop the PBDICHANNEL from the PGM_IF library in to the Control Module containing the
C300 Controller.
10 PROFIBUS GATEWAY MODULE (PGM) CONFIGURATION EXAMPLE
234
www.honeywell.com
Содержание Experion PKS
Страница 1: ...Experion PKS PROFIBUS Gateway Module User s Guide EPDOC XX88 en 431E June 2018 Release 431 ...
Страница 8: ...CONTENTS 8 www honeywell com ...
Страница 10: ...1 ABOUT THIS GUIDE 10 www honeywell com ...
Страница 32: ...4 PROFIBUS GATEWAY MODULE PGM INSTALLATION 32 www honeywell com ...
Страница 58: ...5 PROFIBUS GATEWAY MODULE PGM BLOCK 58 www honeywell com ...
Страница 69: ...6 PROTOCOL BLOCK 69 ...
Страница 103: ...5 Click OK 6 PROTOCOL BLOCK 103 ...
Страница 109: ...You can modify the following value from the Protocol Main tab detail display Alarming Enabled 6 PROTOCOL BLOCK 109 ...
Страница 110: ...6 PROTOCOL BLOCK 110 www honeywell com ...
Страница 181: ...7 20 3 Detail display tab Main tab Figure 4 Detail Display of Main tab 7 DEVICE SUPPORT BLOCK DSB 181 ...
Страница 182: ...Slave Status tab Figure 5 Detail Display of Slave Status tab 7 DEVICE SUPPORT BLOCK DSB 182 www honeywell com ...
Страница 183: ...PDC Details tab Figure 6 Detail Display of PDC Details tab 7 DEVICE SUPPORT BLOCK DSB 183 ...
Страница 184: ...DPV1 Details tab Figure 7 Detail Display of DPV1 Details tab 7 DEVICE SUPPORT BLOCK DSB 184 www honeywell com ...
Страница 185: ...Config Details tab Figure 8 Detail Display of Config Details tab 7 DEVICE SUPPORT BLOCK DSB 185 ...
Страница 186: ...7 DEVICE SUPPORT BLOCK DSB 186 www honeywell com ...
Страница 229: ...For a digital channel the detail display appears as follows 9 PROFIBUS I O MODULE PIOMB FUNCTION BLOCK 229 ...
Страница 231: ...9 PROFIBUS I O MODULE PIOMB FUNCTION BLOCK 231 ...
Страница 232: ...9 PROFIBUS I O MODULE PIOMB FUNCTION BLOCK 232 www honeywell com ...
Страница 236: ...10 PROFIBUS GATEWAY MODULE PGM CONFIGURATION EXAMPLE 236 www honeywell com ...
Страница 264: ...13 PROFIBUS GATEWAY MODULE PGM TROUBLESHOOTING 264 www honeywell com ...