DM-9
Monosplit “Wall” Personal Line Constant Speed - Section 6: Diagnostic & Maintenance
YES
YES
YES
YES
NO
NO
YES
YES
YES
NO
NO
YES
NO
YES
YES
NO
NO
YES
YES
NO
Case 7: Indoor Unit and Outdoor Unit do not operate
NO
Indoor Unit and Outdoor
Unit do not operate.
Is the power supply
no problem?
Replace remote control.
Does system operate?
Does the fuse of Indoor
Unit’s PCB burn out?
Does the transformer
has output?
Is there 12V and 5V voltage
on Indoor Unit’s PCB?
Press Emergency button.
Does system operate?
Does the electric switch
cut off after a few
minutes?
Find the reason and
solve the problem.
Replace the failure
component.
Does the electric switch
cut off?
Are interconnection wires
between Indoor Unit and
Outdoor Unit OK?
Is the insulation of
Indoor Unit and Outdoor
Unit no problem?
Is the resistance of each
main component no problem?
Make the power
supply on.
Replace the fuse.
Replace the PCB.
Transformer
must be replaced.
The problem is
solved.
Replace Display’s
IR receiver.
Normal operation.
Reconnect the wires.