Monosplit “Wall” Personal Line Constant Speed - Section 6: Diagnostic & Maintenance
6.2 FLOWCHARTS FOR MALFUNCTIONS’ SOLUTION
YES
NO
NO
Case 1: Malfunction of temperature sensor “Tr” [Indoor Temperature]
Case 2: Malfunction of temperature sensor “TP1” [Indoor heat exchanger’s temperature]
Malfunction of
Tr
sensor.
Check connector of
Tr
on PCB: is it OK?
Measure the resistance of
Tr
(5k
Ω
, 25°C): is it OK?
Connect connector.
Replace
Tr
sensor.
Replace the PCB (Indoor Unit).
PCB (Indoor Unit) broken.
YES
YES
NO
NO
Malfunction of
TP1
sensor.
Check the connector of
TP1
on PCB: is it OK?
Measure the resistance of
TP1
(5k
Ω
, 25°C): is it OK?
Connect connector.
Replace
TP1
sensor.
Replace the PCB (Indoor Unit).
PCB (Indoor Unit) broken.
YES