IN-23
Monosplit “Wall” Personal Line Constant Speed - Section 5: Installation
Distances and splitting level distances
Item
Unit
Description
Measure
Liquid Side
Gas Side
L (one line)
L
Standard
Piping’s diameter
Piping’s diameter
Splitting distance
Piping’s standard distance (on liquid side) for which
no additional charge is required
(*)
Refrigerant pipings
1. Selection of pipings and specifications
Thermally insulate pipings on liquid side and gas side, as according to operation mode, both of them may
reach low temperatures during the system’s operation.
Use close cells’ insulating material, in addition to the material that already wraps the pipings, which is resistant
to temperatures of at least 120°C.
Piping, Gas Side
Piping, Liquid Side
Ø6.35 (1/4”)
Ø9.52 (3/8”)
Max. 15m
3.5m
(*)
NOTE: If splitting distance is more than 3.5m (liquid side), additional charge is: 30g/m of R410A.
Ø6.35mm (1/4”) x 0.8mm
Ø9.52mm (3/8”) x 0.8mm
HKED-HCND 261 G: Limits related to distances and splitting level distances
HCND 261 G
Indoor Unit
(HKED 261 G)
H1
H2
Indoor Unit
(HKED 261 G)
L
L
m
m
m
H2
H1
Splitting level distance between O.U. (higher) and I.U.
Splitting level distance between O.U. (lower) and I.U.
Max. 5m
Max. 5m
OR
Содержание HCND 261 G
Страница 100: ...Notes 1 Monosplit Wall Personal Line Constant Speed Notes Notes ...
Страница 101: ...Notes 2 Monosplit Wall Personal Line Constant Speed Notes Notes ...
Страница 102: ...Notes 3 Monosplit Wall Personal Line Constant Speed Notes Notes ...
Страница 103: ...Notes 4 Monosplit Wall Personal Line Constant Speed Notes Notes ...