DM-8
Monosplit “Wall” Personal Line Constant Speed - Section 6: Diagnostic & Maintenance
YES
YES
NO
NO
YES
YES
YES
YES
YES
YES
NO
NO
NO
NO
NO
YES
NO
NO
Case 6: Indoor Unit does not operate
A malfunction occurs.
Is the power applied
to the Unit?
Check power supply
cables and interconnection
wires.
Check interconnection
wires between Indoor
Unit and Outdoor Unit.
Press ON/OFF button on
IR remote control.
Is power supply normal?
Check the voltage between
“L” & “N” of terminal block.
Does the beeper
beep?
Is Indoor Unit’s
display OFF?
Check PCB Display’s wiring
on control PCB of Indoor Unit.
Is remote control OK?
IR remote control
is defective.
Is Indoor Unit’s
Control PCB OK?
Replace Control PCB.
Is Indoor Unit’s Display
normal?
Does Outdoor Unit operate?
Check compressor.
Is operation OK?
Check: cables
and compressor
condenser.
Normal.
Does Indoor Unit
operate?
Check Error Codes
on the Table.