![Hitachi RAS-(2-6)HVNP1(E) Скачать руководство пользователя страница 79](http://html.mh-extra.com/html/hitachi/ras-2-6-hvnp1-e/ras-2-6-hvnp1-e_service-manual_2139503079.webp)
3 Piping work and
refrigerant charge
65
SMGB0087 rev.0 - 12/2013
3
3.1.4 Brazing work
The most important work in the refrigerant piping installation work is the brazing of the pipes. If it accidentally occurs a
leakage due to a careless brazing process, it will cause clogged capillary pipes or serious compressor failure.
In order to guarantee a proper brazing neck between different pipes surfaces, accurate pipe dimensions after the expan-
sion process (see the table below):
It is important to control the clearance of the pipe fitting portion as shown below. In the case that a cooper tube expansion
jig is used, following dimensions should be secured.
Copper pipe size
Ød1
Gap
a
Copper pipe size
Ød1
Gap
a
Ø6.35
+0.08
Ø6.5
+0.1
0.33
6
Ø22.22
+0.09
Ø22.42
+0.1
0.39
10
-0.08
0
0.07
-0.09
0
0.11
Ø9.52
+0.08
Ø9.7
+0.1
0.35
8
Ø25.4
+0.12
Ø25.6
+0.1
0.42
12
-0.08
0
0.09
-0.12
0
0.08
Ø12.7
+0.08
Ø12.9
+0.1
0.38
8
Ø28.58
+0.12
Ø28.78
+0.1
0.42
12
-0.08
0
0.19
-0.12
0
0.08
Ø15.88
+0.09
Ø16.1
+0.1
0.41
8
Ø31.75
+0.12
Ø32.0
+0.1
0.47
12
-0.09
0
0.13
-0.12
0
0.13
Ø19.05
+0.09
Ø19.3
+0.1
0.44
10
Ø38.1
+0.12
Ø38.3
+0.1
0.52
14
-0.09
0
0.16
-0.12
0
0.18
A basic brazing method is shown below.
1. Pre-heat the outer tube for better flowing of the filler metal.
2. Heat inner side tube evenly.
3. Rubber plug.
4. Packless valve.
5. High pressure hose.
6. 0.03 to 0.05 MPa (0.3 to 0.5 Kg/cm
2
G).
7. Reducer valve: open this valve only when the gas is needed.
8. Nitrogen gas flow 0.05 m
3
/h or smaller.
C A U T I O N
• Use nitrogen gas for blowing during pipe brazing. If oxygen, acetylene or fluorocarbon gas is used, it will cause an
explosion or poisonous gas.
• During the brazing work, a lot of oxidation film will be generated inside of the pipes if no oxygen-free nitrogen gas is
blown through the pipes. This film will be flecked off after operation and will circulate in the refrigeration cycle, resulting
in clogged expansion valves, etc. This could origin problems in the compressor.
• Use a reducer valve when nitrogen gas blowing is performed during brazing. The gas pressure should be maintained
within 0.03 to 0.05 MPa. If an excessively high pressure is applied to a pipe, it could origin an explosion.
Содержание RAS-(2-6)HVNP1(E)
Страница 2: ......
Страница 4: ... II ...
Страница 28: ......
Страница 134: ...4 Electrical wiring 120 SMGB0087 rev 0 12 2013 4 7 3 RAS 3HVNP1E 1 230V 50Hz XEK01261_0 ...
Страница 136: ...4 Electrical wiring 122 SMGB0087 rev 0 12 2013 4 7 4 RAS 4 6 HVNP1E 1 230V 50Hz XEK01262_1 ...
Страница 138: ...4 Electrical wiring 124 SMGB0087 rev 0 12 2013 4 7 6 RAS 4 6 HNP1E 3N 400V 50Hz XEK01263_2 ...
Страница 140: ...4 Electrical wiring 126 SMGB0087 rev 0 12 2013 4 7 7 RAS 4 6 HVNC1E 1 230V 50Hz XEK01264_4 ...
Страница 142: ...4 Electrical wiring 128 SMGB0087 rev 0 12 2013 4 7 8 RAS 4 6 HNC1E 3N 400V 50Hz XEK01265_4 ...
Страница 144: ...4 Electrical wiring 130 SMGB0087 rev 0 12 2013 4 7 10 RAS 8 10 HN P C E 3N 400V 50Hz XEK01288_3 ...
Страница 146: ...4 Electrical wiring 132 SMGB0087 rev 0 12 2013 4 7 12 RAS 12HN P C 3N 400V 50Hz 7T146440 ...
Страница 148: ......
Страница 204: ......
Страница 220: ......
Страница 332: ......
Страница 353: ...9 Spare parts 339 SMGB0087 rev 0 12 2013 9 RAS 8 10 HNCE Spare Parts Document EPN 201211D ...
Страница 354: ...9 Spare parts 340 SMGB0087 rev 0 12 2013 9 6 2 Electrical parts View from P Spare Parts Document EPN 201211D ...
Страница 362: ......
Страница 484: ......
Страница 496: ......
Страница 497: ......