8 Troubleshooting
314
SMGB0087 rev.0 - 12/2013
4-way solenoid
valve coil
4-way solenoid
valve coil
Time Chart
Heating operation
Cooling operation
or
Defrost operation
Heating operation
4-way solenoid valve
Coil voltage
is turned ON
Current is continuously
carried while the reversing
valve is ON.
Bistable solenoid operation type (pulse-activated)
Operation Mode: Cooling → Heating
Reversing Valve: OFF → ON
Operation Mode: Cooling → Heating
Reversing Valve: OFF → ON
When current is applied to the reversing valve coil, an electro-
magnetic force headed in the same direction as the magnetic
force is generated, and the valve is turned ON by their attraction.
After the valve is turned ON, the plunger position is kept by mag-
netic force with no current applied.
When current is applied to the reversing valve coil, an electro-
magnetic force headed in the direction opposite to the magnetic
force is generated, and the valve is turned OFF by their separa-
tion force. After the valve is turned OFF, the plunger position is
kept by spring force.
Coil Attractor
Plunger
Plunger position
Coil case
Magnetic
screw
Spring force (separation force)
Electromagnetic force (Posi-
tion-keeping force)
Spacer
Magnet
MElectromagnetic
force (Attraction)
When the reversing valve is
turned ON (Current Applied)
After the reversing valve is
turned ON (No Current Applied)
Coil
Attractor
Plunger
Plunger position
Coil case
Magnetic
screw
Electromagnetic force
(separation force)
Spring force (Position-keeping force)
Spacer
Magnet
Magnetic force (Attraction)
When the reversing valve is
turned ON (Current Applied)
After the reversing valve is
turned ON (No Current Applied)
Electrical circuit
When the reversing valve relay is turned ON, current is applied to
the coil. After the reversing valve relay is turned OFF, no current
is applied.
When the reversing valve relay is turned ON, current is applied to
the coil. After the reversing valve relay is turned OFF, no current
is applied.
Содержание RAS-(2-6)HVNP1(E)
Страница 2: ......
Страница 4: ... II ...
Страница 28: ......
Страница 134: ...4 Electrical wiring 120 SMGB0087 rev 0 12 2013 4 7 3 RAS 3HVNP1E 1 230V 50Hz XEK01261_0 ...
Страница 136: ...4 Electrical wiring 122 SMGB0087 rev 0 12 2013 4 7 4 RAS 4 6 HVNP1E 1 230V 50Hz XEK01262_1 ...
Страница 138: ...4 Electrical wiring 124 SMGB0087 rev 0 12 2013 4 7 6 RAS 4 6 HNP1E 3N 400V 50Hz XEK01263_2 ...
Страница 140: ...4 Electrical wiring 126 SMGB0087 rev 0 12 2013 4 7 7 RAS 4 6 HVNC1E 1 230V 50Hz XEK01264_4 ...
Страница 142: ...4 Electrical wiring 128 SMGB0087 rev 0 12 2013 4 7 8 RAS 4 6 HNC1E 3N 400V 50Hz XEK01265_4 ...
Страница 144: ...4 Electrical wiring 130 SMGB0087 rev 0 12 2013 4 7 10 RAS 8 10 HN P C E 3N 400V 50Hz XEK01288_3 ...
Страница 146: ...4 Electrical wiring 132 SMGB0087 rev 0 12 2013 4 7 12 RAS 12HN P C 3N 400V 50Hz 7T146440 ...
Страница 148: ......
Страница 204: ......
Страница 220: ......
Страница 332: ......
Страница 353: ...9 Spare parts 339 SMGB0087 rev 0 12 2013 9 RAS 8 10 HNCE Spare Parts Document EPN 201211D ...
Страница 354: ...9 Spare parts 340 SMGB0087 rev 0 12 2013 9 6 2 Electrical parts View from P Spare Parts Document EPN 201211D ...
Страница 362: ......
Страница 484: ......
Страница 496: ......
Страница 497: ......