8 Troubleshooting
209
SMGB0087 rev.0 - 12/2013
8
8.1.2 Failure of the power supply to the indoor unit and the remote control switch
• The LED and the LCD are not indicated.
• Not operated
If the fuses are blown out or a breaker is activated, investigate the cause of the overcurrent and take the necessary action.
Phenomenon
Cause
Check item
Action
(Turn OFF the main switch)
Power failure or power is not ON
Measure the voltage by means
of the voltmeter
Supply the power
Blown out fuse or activation
of the breaker at the power
source
Short circuit supplied between
the wires
Check for any uncovered part
of the wires
Remove the cause of the short
circuit and replace the fuse
Short circuit of the wires to
earth
Measure the insulation
resistance
Remove the cause of the short
circuit and replace the fuse
Failure of indoor unit fan motor
Measure resistance between
wires and insulation resistance Replace the fan motor and fuse
Blown out fuse at the control
circuit
Short circuit supplied between
the wires
Check for any uncovered part
of the wires
Remove the cause of the short
circuit and replace the fuse
Short circuit of the control
circuit to earth
Measure the insulation
resistance
Remove the cause of the short
circuit and replace the fuse
Failure of indoor unit fan motor
Measure the insulation
resistance
Remove the cause of the short
circuit and replace the fuse
Failure of the transformer at the indoor unit side
Measure the voltage at the
secondary side
Replace the transformer
Disconnected cable of the remote control switch
Connect the cable
Replace the cable or repair the
cable
Insufficient contacting at the
connectors of the remote
control switch
Insufficient connection or
incorrect connection of the
indoor unit PCB
Check the connectors
Correctly connect the
connector
Insufficient connection or
incorrect connection of the
indoor unit PCB in the remote
control switch
Failure of the remote control switch
Check the remote control
switch by means of the
self-check mode *1)
Replace the remote control
switch if it failed
Failure of PCB
Unconnected wires to PCB
Check the connectors
Correctly connect the wires
Failure of PCB
Check PCB by means of the
self-check mode *2)
Replace PCB if it failed
Incorrect wiring connection
Take action according to the procedure that is displayed in
“7. Test run”
N O T E
• *1): Refer to section
“Self-checking procedure of the remote control switch”
.
• *2): Refer to section
“Self-checking procedure of PCB by means of the Remote Control Switch”
.
Содержание RAS-(2-6)HVNP1(E)
Страница 2: ......
Страница 4: ... II ...
Страница 28: ......
Страница 134: ...4 Electrical wiring 120 SMGB0087 rev 0 12 2013 4 7 3 RAS 3HVNP1E 1 230V 50Hz XEK01261_0 ...
Страница 136: ...4 Electrical wiring 122 SMGB0087 rev 0 12 2013 4 7 4 RAS 4 6 HVNP1E 1 230V 50Hz XEK01262_1 ...
Страница 138: ...4 Electrical wiring 124 SMGB0087 rev 0 12 2013 4 7 6 RAS 4 6 HNP1E 3N 400V 50Hz XEK01263_2 ...
Страница 140: ...4 Electrical wiring 126 SMGB0087 rev 0 12 2013 4 7 7 RAS 4 6 HVNC1E 1 230V 50Hz XEK01264_4 ...
Страница 142: ...4 Electrical wiring 128 SMGB0087 rev 0 12 2013 4 7 8 RAS 4 6 HNC1E 3N 400V 50Hz XEK01265_4 ...
Страница 144: ...4 Electrical wiring 130 SMGB0087 rev 0 12 2013 4 7 10 RAS 8 10 HN P C E 3N 400V 50Hz XEK01288_3 ...
Страница 146: ...4 Electrical wiring 132 SMGB0087 rev 0 12 2013 4 7 12 RAS 12HN P C 3N 400V 50Hz 7T146440 ...
Страница 148: ......
Страница 204: ......
Страница 220: ......
Страница 332: ......
Страница 353: ...9 Spare parts 339 SMGB0087 rev 0 12 2013 9 RAS 8 10 HNCE Spare Parts Document EPN 201211D ...
Страница 354: ...9 Spare parts 340 SMGB0087 rev 0 12 2013 9 6 2 Electrical parts View from P Spare Parts Document EPN 201211D ...
Страница 362: ......
Страница 484: ......
Страница 496: ......
Страница 497: ......