8 Troubleshooting
316
SMGB0087 rev.0 - 12/2013
Checking procedure for the compressor
CHECK LIST ON COMPRESSOR
Client:
Model:
Date:
Serie number:
Production date:
Checker:
No.
Check item
Check method
Result
Remarks
1
Is THM9 correctly connected?
THM9: Discharge Gas Thermistor
1. Is wire of thermistor correctly connected by view-
ing?
2. Check to ensure the 7-segment indication of Td
when comp. is operating.
Td: Temperature of THM9
2
Is thermistor THM9 disconnected?
1. Check to ensure that thermistor on the top of
comp. is correctly mounted by viewing?
2. Check to ensure that actually measured tempera-
ture is the same as the indication during check
mode.
3
Is current sensor faulty?
1. Check to ensure that indication A1 and A2 are 0
during compressor stopping.
2. Check to ensure that indication A1 and A2 are not
0 during compressor running.
4
Is current sensing part on PCB2
faulty?
5
Is the direction of current sensor
CTU, CTV) reverse?
Check the direction => by viewing.
6
Are power source wires, U and V in-
serted correctly into current sensor?
Check to ensure that wires are correctly inserted
7
Is expansion valve (MV1) correctly
connected?
Check to ensure that MV1 to CN5A is correctly con-
nected
8
Is expansion valve coil (MV1) cor-
rectly connected?
Check to ensure that each coil is correctly mounted on
the valve.
9
Are the refrigeration cycle and
electrical wiring system incorrectly
connected?
Check to ensure that refrigerant is flowing into indoor
units by operating one refrigerating cycle only from the
outdoor unit.
10
Is opening of expansion valve
completely closed (locked)?
Check the following by the check mode of outdoor
units.
1. Liquid pipe temperature (TL) < Air Intake tempera-
ture (Ti) during cooling operation
2. Liquid pipe temperature (TL) > Air Intake tempera-
ture (Ti) during heating operation
11
Is opening of expansion valve fully
opened locked)?
Check to ensure that liquid pipe temperature is lower
than air intake temperature of stopping indoor unit
when other indoor units are operating under cooling
operation.
12
Are the contacts for comp. magnetic
switch CMC1 faulty?
Check the surface of each contact (L1, L2 and L3) by
viewing.
13
Is there any voltage abnormality
among L1-L2, L2-L3 and L3-L1?
Check to ensure that voltage imbalance is smaller
than 3%.
Please note that power source voltage must be within
380V or 220V+10%.
14
Is the comp. oil acidified during
compressor motor burning?
Check to ensure that the oil color is not black.
Содержание RAS-(2-6)HVNP1(E)
Страница 2: ......
Страница 4: ... II ...
Страница 28: ......
Страница 134: ...4 Electrical wiring 120 SMGB0087 rev 0 12 2013 4 7 3 RAS 3HVNP1E 1 230V 50Hz XEK01261_0 ...
Страница 136: ...4 Electrical wiring 122 SMGB0087 rev 0 12 2013 4 7 4 RAS 4 6 HVNP1E 1 230V 50Hz XEK01262_1 ...
Страница 138: ...4 Electrical wiring 124 SMGB0087 rev 0 12 2013 4 7 6 RAS 4 6 HNP1E 3N 400V 50Hz XEK01263_2 ...
Страница 140: ...4 Electrical wiring 126 SMGB0087 rev 0 12 2013 4 7 7 RAS 4 6 HVNC1E 1 230V 50Hz XEK01264_4 ...
Страница 142: ...4 Electrical wiring 128 SMGB0087 rev 0 12 2013 4 7 8 RAS 4 6 HNC1E 3N 400V 50Hz XEK01265_4 ...
Страница 144: ...4 Electrical wiring 130 SMGB0087 rev 0 12 2013 4 7 10 RAS 8 10 HN P C E 3N 400V 50Hz XEK01288_3 ...
Страница 146: ...4 Electrical wiring 132 SMGB0087 rev 0 12 2013 4 7 12 RAS 12HN P C 3N 400V 50Hz 7T146440 ...
Страница 148: ......
Страница 204: ......
Страница 220: ......
Страница 332: ......
Страница 353: ...9 Spare parts 339 SMGB0087 rev 0 12 2013 9 RAS 8 10 HNCE Spare Parts Document EPN 201211D ...
Страница 354: ...9 Spare parts 340 SMGB0087 rev 0 12 2013 9 6 2 Electrical parts View from P Spare Parts Document EPN 201211D ...
Страница 362: ......
Страница 484: ......
Страница 496: ......
Страница 497: ......