4 Electrical wiring
108
SMGB0087 rev.0 - 12/2013
4.4 Electrical settings
4.4.1 Outdoor and indoor unit electrical wiring
• Connect the electrical wires (indoor unit and the outdoor unit) as show in the figure.
• When installing the electrical wiring, follow local codes and regulations.
• The refrigerant piping and the control wiring are connected to the units in the same refrigerant cycle.
• Use twist pair wire (more than 0.75 mm
2
) for operation wiring between the outdoor unit and indoor unit, and operation
wiring between indoor unit and indoor unit.
• Use a 2-core wire for the operating line (do not use wire with more than 3 cores).
• Use shielded wires for intermediate wiring to protect the units from noise interference at lengths of less than 300 m.
The size must comply with local code.
• Open a hole near the connection hole of power source wiring when multiple outdoor units are connected from a single
power source line.
• The recommended breaker sizes are detailed in the Wire size section.
• In the case that a conduit tube for field-wiring is not used, fix rubber bushes with adhesive on the panel.
• All field wiring and equipment must comply with local and international codes.
• H-LINK twist pair shielded cable must be grounded in the outdoor unit side.
C A U T I O N
Take care with the connection of the operating line. Incorrect connection may cause a failure of the PCB.
Power source from the outdoor unit to the indoor unit
Independent power source of outdoor unit and indoor unit
3
3
3
L1 L2 L3 N
L1 L2 L3 N
L1 L2 L3 N
Number 0 System
Outdoor unit
Number 0 System
Outdoor unit
Operating Line
(Shielded Pair Cable)
DC5V (Non-Pole Transmission,
H-LINK System)
Remote control switch
(Twisted shielded pair cable)
Operating line
(Twisted shielded pair cable)
DC5V (Non-Pole
Transmission,
H-LINK System)
Indoor Unit
Indoor Unit
Terminal board
Circuit breaker
Earthleakage breaker
Field wiring
Field supplied
Optional accessory
Remote control switch
(Twisted shielded pair cable)
Indoor Unit
Indoor Unit
Содержание RAS-(2-6)HVNP1(E)
Страница 2: ......
Страница 4: ... II ...
Страница 28: ......
Страница 134: ...4 Electrical wiring 120 SMGB0087 rev 0 12 2013 4 7 3 RAS 3HVNP1E 1 230V 50Hz XEK01261_0 ...
Страница 136: ...4 Electrical wiring 122 SMGB0087 rev 0 12 2013 4 7 4 RAS 4 6 HVNP1E 1 230V 50Hz XEK01262_1 ...
Страница 138: ...4 Electrical wiring 124 SMGB0087 rev 0 12 2013 4 7 6 RAS 4 6 HNP1E 3N 400V 50Hz XEK01263_2 ...
Страница 140: ...4 Electrical wiring 126 SMGB0087 rev 0 12 2013 4 7 7 RAS 4 6 HVNC1E 1 230V 50Hz XEK01264_4 ...
Страница 142: ...4 Electrical wiring 128 SMGB0087 rev 0 12 2013 4 7 8 RAS 4 6 HNC1E 3N 400V 50Hz XEK01265_4 ...
Страница 144: ...4 Electrical wiring 130 SMGB0087 rev 0 12 2013 4 7 10 RAS 8 10 HN P C E 3N 400V 50Hz XEK01288_3 ...
Страница 146: ...4 Electrical wiring 132 SMGB0087 rev 0 12 2013 4 7 12 RAS 12HN P C 3N 400V 50Hz 7T146440 ...
Страница 148: ......
Страница 204: ......
Страница 220: ......
Страница 332: ......
Страница 353: ...9 Spare parts 339 SMGB0087 rev 0 12 2013 9 RAS 8 10 HNCE Spare Parts Document EPN 201211D ...
Страница 354: ...9 Spare parts 340 SMGB0087 rev 0 12 2013 9 6 2 Electrical parts View from P Spare Parts Document EPN 201211D ...
Страница 362: ......
Страница 484: ......
Страница 496: ......
Страница 497: ......