7 Test run
203
SMGB0087 rev.0 - 12/2013
7
7.6 Check list
7.6.1 Check list on test run
MODEL:
SERIAL NUMBER:
COMPRESSOR MFG NUMBER:
NAME AND ADDRESS OF CUSTOMER:
DATE:
1
Is the rotation direction of the indoor coil fan correct? __________
2
Is the rotation direction of the outdoor coil fan correct? __________
3
Is there any abnormal compressor sound? __________
4
Has the unit been operating for at least twenty (20) minutes? __________
5
Check the room temperature:
Inlet
Number 1
DB ____ ºC
WB ____ ºC
Number 2
DB ____ ºC
WB ____ ºC
Number 3
DB ____ ºC
WB ____ ºC
Number 4
DB ____ ºC
WB ____ ºC
Outlet
DB ____ ºC
WB ____ ºC
DB ____ ºC
WB ____ ºC
DB ____ ºC
WB ____ ºC
DB ____ ºC
WB ____ ºC
Inlet
Number 5
DB ____ ºC
WB ____ ºC
Number 6
DB ____ ºC
WB ____ ºC
Number 7
DB ____ ºC
WB ____ ºC
Number 8
DB ____ ºC
WB ____ ºC
Outlet
DB ____ ºC
WB ____ ºC
DB ____ ºC
WB ____ ºC
DB ____ ºC
WB ____ ºC
DB ____ ºC
WB ____ ºC
6
Check the outdoor ambient temperature:
Inlet
DB ____ ºC
WB ____ ºC
Outlet
DB____ ºC
WB ____ ºC
7
Check the refrigerant temperature: Operating mode (cool or heat):
Discharge gas temperature
Td = _____ ºC
Liquid pipe temperature
Te = _____ ºC
8
Check the pressure:
Discharge pressure
Pd = _____kg/cm
2
G
Suction pressure
Ps = _____kg/cm
2
G
9
Check the voltage:
Rated voltage
_____V
—
—
Operating voltage
L1–L2 ______V
L1–L3______V
L2–L3______V
Starting voltage
_____V
—
—
Phase imbalance
1-(V/Vm) =
—
—
10
Check the compressor input running current:
Input
_____kW
Running current
_____A
11
Is the refrigerant charge adequate? __________
12
Do the operation control devices operate correctly? __________
13
Do the safety devices operate correctly? __________
14
Has the unit been checked for refrigerant leakage? __________
15
Is the unit clean inside and outside? __________
16
Are all the cabinet panels fixed? __________
17
Are all the cabinet panels free from rattles? __________
18
Is the filter clean? __________
19
Is the heat exchanger clean? __________
20
Are the stop valves open? __________
21
Does the drain water flow smoothly from the drain pipe? __________
Содержание RAS-(2-6)HVNP1(E)
Страница 2: ......
Страница 4: ... II ...
Страница 28: ......
Страница 134: ...4 Electrical wiring 120 SMGB0087 rev 0 12 2013 4 7 3 RAS 3HVNP1E 1 230V 50Hz XEK01261_0 ...
Страница 136: ...4 Electrical wiring 122 SMGB0087 rev 0 12 2013 4 7 4 RAS 4 6 HVNP1E 1 230V 50Hz XEK01262_1 ...
Страница 138: ...4 Electrical wiring 124 SMGB0087 rev 0 12 2013 4 7 6 RAS 4 6 HNP1E 3N 400V 50Hz XEK01263_2 ...
Страница 140: ...4 Electrical wiring 126 SMGB0087 rev 0 12 2013 4 7 7 RAS 4 6 HVNC1E 1 230V 50Hz XEK01264_4 ...
Страница 142: ...4 Electrical wiring 128 SMGB0087 rev 0 12 2013 4 7 8 RAS 4 6 HNC1E 3N 400V 50Hz XEK01265_4 ...
Страница 144: ...4 Electrical wiring 130 SMGB0087 rev 0 12 2013 4 7 10 RAS 8 10 HN P C E 3N 400V 50Hz XEK01288_3 ...
Страница 146: ...4 Electrical wiring 132 SMGB0087 rev 0 12 2013 4 7 12 RAS 12HN P C 3N 400V 50Hz 7T146440 ...
Страница 148: ......
Страница 204: ......
Страница 220: ......
Страница 332: ......
Страница 353: ...9 Spare parts 339 SMGB0087 rev 0 12 2013 9 RAS 8 10 HNCE Spare Parts Document EPN 201211D ...
Страница 354: ...9 Spare parts 340 SMGB0087 rev 0 12 2013 9 6 2 Electrical parts View from P Spare Parts Document EPN 201211D ...
Страница 362: ......
Страница 484: ......
Страница 496: ......
Страница 497: ......