192
SMGB0087 rev.0 - 12/2013
7.1 Checking procedure before the test run
When you have finished the installation, perform the test run according to the following procedure. After performing the test
run, hand over the system to the customer.
Perform the test run of the indoor units one by one in order.
Make sure that the electrical wiring and the refrigerant piping are correctly connected.
Start the indoor units one by one in order to make sure that the indoor units are correctly numbered.
You should perform the test run according to
“7.2 Test run procedure using the remote control switch (PC-ART)”
on next
pages.
D A N G E R
• Do not operate the system until all the check points have been cleared.
• Measure the resistance between the ground and the terminal of the electrical components. Make sure that
the electrical resistance is more than 1 MΩ. Otherwise, do not operate the system until you find the electrical
leakage and you repair the electrical leakage. Do not apply voltage on the terminals for transmission 1 and 2. (*)
• Pay attention to the following items while the system is running.
-
Do not touch any of the parts at the discharge gas side with your hands because the compressor chamber
and the pipes at the discharge gas side are hot at a temperature that is higher than 90ºC.
-
DO NOT PUSH THE BUTTON OF THE MAGNETIC SWITCH(ES). If you do, you will cause a serious accident.
• Do not touch any electrical components for more than three minutes after turning OFF the main switch.
Checking procedure
1
Make sure that the stop valve of the gas line and the stop valve of the liquid line are fully open.
2
Make sure that there is no refrigerant leakage. The flare nuts sometimes loosen because of the vibration during the
transportation.
3
Make sure that the refrigerant piping and the electrical wiring belong to the same system. Make sure that the setting of
the unit number of DSW1, DSW6 and RSW1 of indoor units correspond to the system.
4
Make sure that the setting of the DIP switches on the printed circuit board of the indoor units and the outdoor units are
correct. Especially, pay attention to the setting of the lift between the indoor units and the outdoor units. Refer to chapter
“4. Electrical wiring”
for details.
5
Make sure that the switch on the main power source has been ON for more than twelve hours in order to warm the
compressor oil by means of the oil heater.
6
Check whether or not the electrical wiring of the indoor units and the outdoor units are connected as shown in chapter
7
“4. Electrical wiring”
.
8
Make sure that each wire terminal (L1,L2,L3 and N or L1 and N) is correctly connected at the power source.
N O T E
• Make sure that the field-supplied electrical components (main switch fuse, fuse-free breaker, earth leakage breaker,
wires, conduit connectors and wire terminals) have been properly selected according to the electrical data in the tech-
nical catalogue of the unit. Also, make sure that the field-supplied electrical components comply with the national codes
and the local codes.
• Use the shielded cables for the field transmission wiring in order to avoid the electrical noise. (The length of the shielded
cable should be less than 1000 m. The size of shielded cable should comply with the local codes).
• Make sure that the terminals for the power supply wiring (“L1” to “L1” and “N” to “N” of each terminal board for AC 230 V
and the terminals for the intermediate wires between the indoor unit and the outdoor unit (Operating Line: terminals of
each terminal board for DC 12 V) match correctly. Otherwise, you may damage some components.
• For RAS-12HN(P/C) units, the operation may not be available within 4 hours after turning ON the power supply due to
the unheated crankcase (stoppage code: d1-22). If the compressor should be within 4 hours, turn ON the power and
wait for more than 30 seconds. Press PSW1 and PSW3 on the outdoor PCB simultaneously for more than 3 seconds.
The forced thermo-OFF function (d1-22) is cancelled and the compressor operation is available.
Содержание RAS-(2-6)HVNP1(E)
Страница 2: ......
Страница 4: ... II ...
Страница 28: ......
Страница 134: ...4 Electrical wiring 120 SMGB0087 rev 0 12 2013 4 7 3 RAS 3HVNP1E 1 230V 50Hz XEK01261_0 ...
Страница 136: ...4 Electrical wiring 122 SMGB0087 rev 0 12 2013 4 7 4 RAS 4 6 HVNP1E 1 230V 50Hz XEK01262_1 ...
Страница 138: ...4 Electrical wiring 124 SMGB0087 rev 0 12 2013 4 7 6 RAS 4 6 HNP1E 3N 400V 50Hz XEK01263_2 ...
Страница 140: ...4 Electrical wiring 126 SMGB0087 rev 0 12 2013 4 7 7 RAS 4 6 HVNC1E 1 230V 50Hz XEK01264_4 ...
Страница 142: ...4 Electrical wiring 128 SMGB0087 rev 0 12 2013 4 7 8 RAS 4 6 HNC1E 3N 400V 50Hz XEK01265_4 ...
Страница 144: ...4 Electrical wiring 130 SMGB0087 rev 0 12 2013 4 7 10 RAS 8 10 HN P C E 3N 400V 50Hz XEK01288_3 ...
Страница 146: ...4 Electrical wiring 132 SMGB0087 rev 0 12 2013 4 7 12 RAS 12HN P C 3N 400V 50Hz 7T146440 ...
Страница 148: ......
Страница 204: ......
Страница 220: ......
Страница 332: ......
Страница 353: ...9 Spare parts 339 SMGB0087 rev 0 12 2013 9 RAS 8 10 HNCE Spare Parts Document EPN 201211D ...
Страница 354: ...9 Spare parts 340 SMGB0087 rev 0 12 2013 9 6 2 Electrical parts View from P Spare Parts Document EPN 201211D ...
Страница 362: ......
Страница 484: ......
Страница 496: ......
Страница 497: ......