8 Troubleshooting
257
SMGB0087 rev.0 - 12/2013
8
Phenomenon
Cause
Check item
Action
(Turn OFF Main Switch)
Activation of High Pressure
Switch due to Excessively High
Discharge Pressure during
Heating Operation
Insufficient Air Flow to Heat
Exchanger of Indoor Unit
Clogging of Heat Exchanger
Remove it
Check for dust on air filter
Check for any obstacle at inlet
or outlet of heat exchanger
Check the service space
Secure service space
Check for indoor fan speed
Replace fan motor if faulty
Activation of High Pressure
Switch due to Excessively High
Discharge Pressure during
Heating Operation
Excessively High Temperature
Air to Indoor Unit Heat Ex-
changer
Calculate heat load
Reduce heat load or use a big-
ger unit
Check for hot air near the
ceiling
Make good circulation
Check for short circuited air
Remove short-circuited air
Check for other heat source
Remove heat source
Faulty high
pressure
switch
Faulty
pressure
switch
Measure discharge pressure.
Check continuity after decreas-
ing of pressure
Replace it if faulty
Insufficient
contacting
Measure resistance by tester
Repair looseness.
Replace connector
Incorrect
connection
Check connections
Repair connections
Faulty of Outdoor Fan Control
Check decreasing air flow
volume at pressure switch for
control activative
Replace thermistor for
evaporating temperature if
faulty
Faulty of Pressure Switch for
Control
Check activated pressure and
connecting wire
Replace it if pressure switch for
control is faulty
Overcharged Refrigerant
Check cycle operating
temperature
Charge refrigerant correctly
Mixture of Non-Condensable
Gas in Refrigerant Cycle
Check ambient temperature
and pressure
Recharge refrigerant after
vacuum pumping
Clogging of Discharge Piping
Check for clogging
Remove clogging
Faulty or Malfunction of
Expansion Valve
Check for clogging
Remove clogging
Check connecting wiring and
connectors
Replace connector
Check operating sound from
coil
Replace coil
Check discharge gas
thermistor
Replace thermistor
Check attaching state of
discharge gas thermistor
Reattach thermistor
Liquid Line Stop Valve or Gas
Line Stop Valve are not in
Operation
Check stop valves
Fully open stop valve
N O T E
This alarm code is indicated when the outdoor unit protective device is activated by high discharge pressure during heating
operation. Accordingly, when this alarm code is indicated, there is high possibility of high pressure switch actuation and the
above troubleshooting actions are based on such cases.
Содержание RAS-(2-6)HVNP1(E)
Страница 2: ......
Страница 4: ... II ...
Страница 28: ......
Страница 134: ...4 Electrical wiring 120 SMGB0087 rev 0 12 2013 4 7 3 RAS 3HVNP1E 1 230V 50Hz XEK01261_0 ...
Страница 136: ...4 Electrical wiring 122 SMGB0087 rev 0 12 2013 4 7 4 RAS 4 6 HVNP1E 1 230V 50Hz XEK01262_1 ...
Страница 138: ...4 Electrical wiring 124 SMGB0087 rev 0 12 2013 4 7 6 RAS 4 6 HNP1E 3N 400V 50Hz XEK01263_2 ...
Страница 140: ...4 Electrical wiring 126 SMGB0087 rev 0 12 2013 4 7 7 RAS 4 6 HVNC1E 1 230V 50Hz XEK01264_4 ...
Страница 142: ...4 Electrical wiring 128 SMGB0087 rev 0 12 2013 4 7 8 RAS 4 6 HNC1E 3N 400V 50Hz XEK01265_4 ...
Страница 144: ...4 Electrical wiring 130 SMGB0087 rev 0 12 2013 4 7 10 RAS 8 10 HN P C E 3N 400V 50Hz XEK01288_3 ...
Страница 146: ...4 Electrical wiring 132 SMGB0087 rev 0 12 2013 4 7 12 RAS 12HN P C 3N 400V 50Hz 7T146440 ...
Страница 148: ......
Страница 204: ......
Страница 220: ......
Страница 332: ......
Страница 353: ...9 Spare parts 339 SMGB0087 rev 0 12 2013 9 RAS 8 10 HNCE Spare Parts Document EPN 201211D ...
Страница 354: ...9 Spare parts 340 SMGB0087 rev 0 12 2013 9 6 2 Electrical parts View from P Spare Parts Document EPN 201211D ...
Страница 362: ......
Страница 484: ......
Страница 496: ......
Страница 497: ......