3 Piping work and
refrigerant charge
89
SMGB0087 rev.0 - 12/2013
3
3.5 Caution in case of refrigerant leakage
The installers and those responsible for drafting the specifications are obliged to comply with local safety codes and regu-
lations in the case of refrigerant leakage.
3.5.1 Maximum permitted concentration of hydrofluorocarbon (HFC)
The refrigerant R410A, charged in the UTOPIA series system, is an incombustible and non-toxic gas. However, if leakage
occurs and gas fills a room, it may cause suffocation.The maximum permissible concentration of HFC gas, R410A in air
is 0.44 kg/m
3
, according to EN378-1.
Therefore, some effective measure must be taken to lower the R410A concentration in air below 0.44 kg/m
3
to prevent
suffocation in case of leakage.
3.5.2 Calculation of refrigerant concentration
1
Calculate the total quantity of refrigerant R (kg) charged in the system by connecting all the indoor units in the rooms
to be air-conditioned.
2
Calculate the room volume V (m
3
) of each room (including false ceiling).
3
Calculate the refrigerant concentration C (kg/m
3
) of the room according to the following equation:
C = R / V
R: Total quantity of refrigerant charged (kg).
V: Room volume (m
3
).
C: Refrigerant concentration (≤ 0.44 kg/m
3
for R410A).
3.5.3 Countermeasure for refrigerant leakage
The room must have the following features to prevent suffocation in case a refrigerant leakage occurs:
1
Provide a shutterless opening which will allow fresh air to circulate into the room.
2
Provide a doorless opening of 0.15% or more size to the floor area.
3
There must be a ventilator fan connected to a gas leak detector, with a ventilator capacity of 0.4 m³/min or higher per
Japanese refrigeration ton (= compressor displacement volume / 5.7 m³/h) of the air conditioning system using the
refrigerant.
IVX Premium series
Model
Tonnes
RAS-2HVNP1
0.88
RAS-2.5HVNP1
0.88
RAS-3HVNP1E
1.17
RAS-(4-6)H(V)NP1E
2.27
RAS-8HNPE
3.16
RAS-10HNPE / RAS-12HNP
4.11
IVX Standard series
Model
Tonnes
RAS-3HVNC1
1.17
RAS-4H(V)NC1E
1.64
RAS-(5/6)H(V)NC1E
2.27
RAS-8HNCE
3.16
RAS-10HNCE / RAS-12HNC
4.11
4
Pay a special attention to the place, such as a basement, etc., where refrigerant can stay, since refrigerant is heavier
than air.
Содержание RAS-(2-6)HVNP1(E)
Страница 2: ......
Страница 4: ... II ...
Страница 28: ......
Страница 134: ...4 Electrical wiring 120 SMGB0087 rev 0 12 2013 4 7 3 RAS 3HVNP1E 1 230V 50Hz XEK01261_0 ...
Страница 136: ...4 Electrical wiring 122 SMGB0087 rev 0 12 2013 4 7 4 RAS 4 6 HVNP1E 1 230V 50Hz XEK01262_1 ...
Страница 138: ...4 Electrical wiring 124 SMGB0087 rev 0 12 2013 4 7 6 RAS 4 6 HNP1E 3N 400V 50Hz XEK01263_2 ...
Страница 140: ...4 Electrical wiring 126 SMGB0087 rev 0 12 2013 4 7 7 RAS 4 6 HVNC1E 1 230V 50Hz XEK01264_4 ...
Страница 142: ...4 Electrical wiring 128 SMGB0087 rev 0 12 2013 4 7 8 RAS 4 6 HNC1E 3N 400V 50Hz XEK01265_4 ...
Страница 144: ...4 Electrical wiring 130 SMGB0087 rev 0 12 2013 4 7 10 RAS 8 10 HN P C E 3N 400V 50Hz XEK01288_3 ...
Страница 146: ...4 Electrical wiring 132 SMGB0087 rev 0 12 2013 4 7 12 RAS 12HN P C 3N 400V 50Hz 7T146440 ...
Страница 148: ......
Страница 204: ......
Страница 220: ......
Страница 332: ......
Страница 353: ...9 Spare parts 339 SMGB0087 rev 0 12 2013 9 RAS 8 10 HNCE Spare Parts Document EPN 201211D ...
Страница 354: ...9 Spare parts 340 SMGB0087 rev 0 12 2013 9 6 2 Electrical parts View from P Spare Parts Document EPN 201211D ...
Страница 362: ......
Страница 484: ......
Страница 496: ......
Страница 497: ......