![Hitachi RAS-(2-6)HVNP1(E) Скачать руководство пользователя страница 461](http://html.mh-extra.com/html/hitachi/ras-2-6-hvnp1-e/ras-2-6-hvnp1-e_service-manual_2139503461.webp)
10 Servicing
447
SMGB0087 rev.0 - 12/2013
10
10.9.10 Removing reversing and solenoid valves coils
1
Remove the service cover following
“10.9.1 Remo-
ving service cover”
in this chapter.
2
Remove the connectors on the control PCB (PCB1)
of the electrical box according to the following pic-
ture.
3
Remove the valve coils by removing 1 fixing screw
for each coil.
4
When reassembling, perform the procedure in the
reverse way of removing.
N O T E
Fix the wires by plastic bands to the original position.
Hold the coil of the
SVA and pull out
upward
Reversing valve coil
Hold the coil of the
reversing valve and pull
out to the right
Hold the coil of
the SVF and pull
out upward
Fixing screws
Rear cover
Upper cover
Electrical box
10.9.11 Removing electronic expansion valve coil
1
Remove the service cover, the bottom service cover and the
rear cover following
“10.9.1 Removing service cover”
and
“10.9.4 Removing the bottom service cover and rear cover”
.
2
Open the P plate turning counter clockwise approximately 90°
following
“10.9.9 Opening electrical box (P-Mounting Plate)”
.
• Check that the LED201 (red) on Inverter is OFF when the
P plate is opened.
3
Disconnect the CN5A connector on the control PCB1 of the
electrical box.
4
Hold the coil of the expansion valve and pull out upward. It is
easier to remove the expansion valve coil if it is rotated while
pulling it upward.
5
When reassembling after replacing the expansion valve coil,
perform the procedure in the reverse way of removing. The
expansion valve coil is equipped with a lock mechanism. After
attaching the expansion valve coil, rotate it until the sound of
locking is heard.
N O T E
Fix the wires by plastic bands to the original position.
Hold the coil of
the expansion
valve and pull
out upward
Expansion valve coil
Release lock
Содержание RAS-(2-6)HVNP1(E)
Страница 2: ......
Страница 4: ... II ...
Страница 28: ......
Страница 134: ...4 Electrical wiring 120 SMGB0087 rev 0 12 2013 4 7 3 RAS 3HVNP1E 1 230V 50Hz XEK01261_0 ...
Страница 136: ...4 Electrical wiring 122 SMGB0087 rev 0 12 2013 4 7 4 RAS 4 6 HVNP1E 1 230V 50Hz XEK01262_1 ...
Страница 138: ...4 Electrical wiring 124 SMGB0087 rev 0 12 2013 4 7 6 RAS 4 6 HNP1E 3N 400V 50Hz XEK01263_2 ...
Страница 140: ...4 Electrical wiring 126 SMGB0087 rev 0 12 2013 4 7 7 RAS 4 6 HVNC1E 1 230V 50Hz XEK01264_4 ...
Страница 142: ...4 Electrical wiring 128 SMGB0087 rev 0 12 2013 4 7 8 RAS 4 6 HNC1E 3N 400V 50Hz XEK01265_4 ...
Страница 144: ...4 Electrical wiring 130 SMGB0087 rev 0 12 2013 4 7 10 RAS 8 10 HN P C E 3N 400V 50Hz XEK01288_3 ...
Страница 146: ...4 Electrical wiring 132 SMGB0087 rev 0 12 2013 4 7 12 RAS 12HN P C 3N 400V 50Hz 7T146440 ...
Страница 148: ......
Страница 204: ......
Страница 220: ......
Страница 332: ......
Страница 353: ...9 Spare parts 339 SMGB0087 rev 0 12 2013 9 RAS 8 10 HNCE Spare Parts Document EPN 201211D ...
Страница 354: ...9 Spare parts 340 SMGB0087 rev 0 12 2013 9 6 2 Electrical parts View from P Spare Parts Document EPN 201211D ...
Страница 362: ......
Страница 484: ......
Страница 496: ......
Страница 497: ......