8 Troubleshooting
255
SMGB0087 rev.0 - 12/2013
8
Phenomenon
Cause
Check item
Action
(Turn OFF main switch)
Activation of high pressure
switch due to excessively
high discharge pressure dur-
ing cooling operation
Insufficient air flow to heat ex-
changer of outdoor unit
Clogging of Heat Exchanger?
Remover clogging
Check for dust on air filter
Remove dust
Check the service space
Secure service space
Check for outdoor fan speed
Replace fan motor if faulty
Excessively high temperature air
to outdoor unit heat exchanger
Check for hot air near the
ceiling
Make good circulation
Check for short circuited air
Remove short-circuited air
Check for other heat source
Remove heat source
Faulty high
pressure
switch
Faulty
pressure
switch
Measure discharge pressure.
Check continuity after
decreasing of pressure
Replace it if faulty
Insufficient
contacting
Measure resistance by tester
Repair looseness.
Replace connector
Incorrect
connection
Check connections
Repair connections
Overcharged refrigerant
Check cycle operating
temperature
Charge refrigerant correctly
Mixture of non-condensable gas
in refrigerant cycle
Check ambient temperature
and pressure
Recharge refrigerant after
vacuum pumping
Clogging of discharge piping
Check for clogging
Remove clogging
Faulty or malfunction of
expansion valve
Check for clogging
Remove clogging
Check connecting wiring and
connectors
Replace connector
Check operating sound from
coil
Replace coil
Check discharge gas
thermistor
Replace thermistor
Check attaching state of
discharge gas thermistor
Reattach thermistor
Liquid line stop valve or gas line
stop valve are not in operation
Check stop valves
Fully open stop valve
Locking up outdoor unit
expansion valve closure
Check expansion valve
actuation
Replace outdoor expansion valve
N O T E
This alarm code is indicated when the outdoor unit protective device is activated by high discharge pressure during cooling
operation. Accordingly, when this alarm code is indicated, there is high possibility of high pressure switch actuation and the
above troubleshooting actions are based on such cases.
Содержание RAS-(2-6)HVNP1(E)
Страница 2: ......
Страница 4: ... II ...
Страница 28: ......
Страница 134: ...4 Electrical wiring 120 SMGB0087 rev 0 12 2013 4 7 3 RAS 3HVNP1E 1 230V 50Hz XEK01261_0 ...
Страница 136: ...4 Electrical wiring 122 SMGB0087 rev 0 12 2013 4 7 4 RAS 4 6 HVNP1E 1 230V 50Hz XEK01262_1 ...
Страница 138: ...4 Electrical wiring 124 SMGB0087 rev 0 12 2013 4 7 6 RAS 4 6 HNP1E 3N 400V 50Hz XEK01263_2 ...
Страница 140: ...4 Electrical wiring 126 SMGB0087 rev 0 12 2013 4 7 7 RAS 4 6 HVNC1E 1 230V 50Hz XEK01264_4 ...
Страница 142: ...4 Electrical wiring 128 SMGB0087 rev 0 12 2013 4 7 8 RAS 4 6 HNC1E 3N 400V 50Hz XEK01265_4 ...
Страница 144: ...4 Electrical wiring 130 SMGB0087 rev 0 12 2013 4 7 10 RAS 8 10 HN P C E 3N 400V 50Hz XEK01288_3 ...
Страница 146: ...4 Electrical wiring 132 SMGB0087 rev 0 12 2013 4 7 12 RAS 12HN P C 3N 400V 50Hz 7T146440 ...
Страница 148: ......
Страница 204: ......
Страница 220: ......
Страница 332: ......
Страница 353: ...9 Spare parts 339 SMGB0087 rev 0 12 2013 9 RAS 8 10 HNCE Spare Parts Document EPN 201211D ...
Страница 354: ...9 Spare parts 340 SMGB0087 rev 0 12 2013 9 6 2 Electrical parts View from P Spare Parts Document EPN 201211D ...
Страница 362: ......
Страница 484: ......
Страница 496: ......
Страница 497: ......