![Hitachi RAS-(2-6)HVNP1(E) Скачать руководство пользователя страница 495](http://html.mh-extra.com/html/hitachi/ras-2-6-hvnp1-e/ras-2-6-hvnp1-e_service-manual_2139503495.webp)
12 Maintenance notes
481
SMGB0087 rev.0 - 12/2013
12
No.
Procedure
Remarks
13
Perform the replacement of the compressor and the change
of the refrigerant oil according to the section “replacing the
compressor”.
Make sure that you follow the instructions.
14
Perform the vacuum from the check joint of the low-pressure
side.
If you collect the refrigerant only on the low-pressure side
(A in 10). You cannot perform the vacuum of the refrigerant
from the check joint of the high-pressure side.
15
Open the liquid stop valve and the gas stop valve comple-
tely when you finish the vacuum.
—
16
Make sure that the power is turned OFF and attach the
following items: the power supply wire the thermistor the
crankcase heater the 63H wiring the panel and the nut).
—
17
Set the DSW back to the original setting. Make sure that all
the wirings to the compressor are connected correctly.
—
18
Recharge the refrigerant that is collected in the process by
the stop valve of the liquid side during the cooling at the
TEST RUN mode.
If the replacement of the compressor takes more than two
hours an additional change of the refrigerant is necessary.
Additional change = (replacing time – 2 hours) x 0.5 kg.
Содержание RAS-(2-6)HVNP1(E)
Страница 2: ......
Страница 4: ... II ...
Страница 28: ......
Страница 134: ...4 Electrical wiring 120 SMGB0087 rev 0 12 2013 4 7 3 RAS 3HVNP1E 1 230V 50Hz XEK01261_0 ...
Страница 136: ...4 Electrical wiring 122 SMGB0087 rev 0 12 2013 4 7 4 RAS 4 6 HVNP1E 1 230V 50Hz XEK01262_1 ...
Страница 138: ...4 Electrical wiring 124 SMGB0087 rev 0 12 2013 4 7 6 RAS 4 6 HNP1E 3N 400V 50Hz XEK01263_2 ...
Страница 140: ...4 Electrical wiring 126 SMGB0087 rev 0 12 2013 4 7 7 RAS 4 6 HVNC1E 1 230V 50Hz XEK01264_4 ...
Страница 142: ...4 Electrical wiring 128 SMGB0087 rev 0 12 2013 4 7 8 RAS 4 6 HNC1E 3N 400V 50Hz XEK01265_4 ...
Страница 144: ...4 Electrical wiring 130 SMGB0087 rev 0 12 2013 4 7 10 RAS 8 10 HN P C E 3N 400V 50Hz XEK01288_3 ...
Страница 146: ...4 Electrical wiring 132 SMGB0087 rev 0 12 2013 4 7 12 RAS 12HN P C 3N 400V 50Hz 7T146440 ...
Страница 148: ......
Страница 204: ......
Страница 220: ......
Страница 332: ......
Страница 353: ...9 Spare parts 339 SMGB0087 rev 0 12 2013 9 RAS 8 10 HNCE Spare Parts Document EPN 201211D ...
Страница 354: ...9 Spare parts 340 SMGB0087 rev 0 12 2013 9 6 2 Electrical parts View from P Spare Parts Document EPN 201211D ...
Страница 362: ......
Страница 484: ......
Страница 496: ......
Страница 497: ......