12.1.5 Alarm code “03”
Question and answer for the field work
Example 4: Alarm code “03”
Phenomenon
Alarm code “31” sometimes occurred and the system stopped.
Cause
The combination of the indoor units and the outdoor unit was the following.
ON
OFF
ON
ON
ON
ON
Power
Source
Power
source
This system was used in a tenant building. One of tenant’s customers turned off the main switch for the indoor
unit while other indoor units are running. This results in a different setting of the total indoor unit capacity in the
same refrigerant cycle.
Countermeasure
All the main switches for the indoor units were always ON.
12.1.6 Not cooling well due to insufficient installation space for the outdoor unit
Question and answer for the field work
Example 5: Not cooling well due to insufficient installation space for outdoor unit
Phenomenon
Cooling operation was well performed through the intermediate season. However the cooling operation was
not well available when the outdoor temperature was higher than 35 °C.
Cause
As the outdoor units were installed without a sufficient installation space the hot discharge air from other out-
door units was circulated.
In this case though the outdoor temperature was 35 °C the actual suction air temperature was nearly 50 °C
and protection system from excessively high suction pressure was activated the frequency of the compressor
was decreased and the cooling capacity was also decreased accordingly.
As the outdoor units in-line were installed back to back with a distance of 600 mm (depending on model)
between each outdoor unit’s back the hot discharged air from other outdoor units was circulated.
Countermeasure
Ensure that sufficient space should be secured for multi-row and multiple-installation.
Example
Keep a distance between other units and do not put obstacles on the right and left sides.
For detailed information please refer to
“2. Unit Installation”
chapter.
Содержание RAS-(2-6)HVNP1(E)
Страница 2: ......
Страница 4: ... II ...
Страница 28: ......
Страница 134: ...4 Electrical wiring 120 SMGB0087 rev 0 12 2013 4 7 3 RAS 3HVNP1E 1 230V 50Hz XEK01261_0 ...
Страница 136: ...4 Electrical wiring 122 SMGB0087 rev 0 12 2013 4 7 4 RAS 4 6 HVNP1E 1 230V 50Hz XEK01262_1 ...
Страница 138: ...4 Electrical wiring 124 SMGB0087 rev 0 12 2013 4 7 6 RAS 4 6 HNP1E 3N 400V 50Hz XEK01263_2 ...
Страница 140: ...4 Electrical wiring 126 SMGB0087 rev 0 12 2013 4 7 7 RAS 4 6 HVNC1E 1 230V 50Hz XEK01264_4 ...
Страница 142: ...4 Electrical wiring 128 SMGB0087 rev 0 12 2013 4 7 8 RAS 4 6 HNC1E 3N 400V 50Hz XEK01265_4 ...
Страница 144: ...4 Electrical wiring 130 SMGB0087 rev 0 12 2013 4 7 10 RAS 8 10 HN P C E 3N 400V 50Hz XEK01288_3 ...
Страница 146: ...4 Electrical wiring 132 SMGB0087 rev 0 12 2013 4 7 12 RAS 12HN P C 3N 400V 50Hz 7T146440 ...
Страница 148: ......
Страница 204: ......
Страница 220: ......
Страница 332: ......
Страница 353: ...9 Spare parts 339 SMGB0087 rev 0 12 2013 9 RAS 8 10 HNCE Spare Parts Document EPN 201211D ...
Страница 354: ...9 Spare parts 340 SMGB0087 rev 0 12 2013 9 6 2 Electrical parts View from P Spare Parts Document EPN 201211D ...
Страница 362: ......
Страница 484: ......
Страница 496: ......
Страница 497: ......