4 Electrical wiring
113
SMGB0087 rev.0 - 12/2013
4
Unit
Name of DIP switch
Mark
Setting before the Shipment
Function
Outdoor
Unit
Refrigerant cycle
DSW4
RSW1
For setting the refrigerant cycle address of
the outdoor unit. Set the DSW4 and RSW1 to
overlap the setting of other outdoor units in
the same H-LINK system.
Resistance of terminal
DSW5
To adapt the impedance of the transmission
circuit, adjust DSW5 according to the number
of outdoor units of the H-LINK system.
Indoor
Unit
Refrigerant cycle
DSW5
RSW2
DSW5
RSW2
For setting the refrigerant cycle address of
the indoor unit. Set the DSW5 and RSW2
corresponding to the address of outdoor unit
in the same refrigerant cycle.
Address of the indoor unit DSW6
RSW1
DSW6
RSW1
Setting indoor unit address. Set the DSW6
and RSW1 not to overlap the setting of other
indoor units in the same refrigerant cycle.
(If no set, the automatic address function is
performed.)
4.5.4 Examples of the system of connection between H-LINK and H-LINK II units
In the case of mixed systems with H-LINK and H-LINK II, set the H-LINK units in the first 16 position of the system, as
in the following example where 42 systems are connected, 16 with indoor FSN1E units and 26 with indoor FSN2E units.
A
A
A
A
A
A
A
A
D
E
F
C
B
D
D
D
A: Refrigerant cycle.
B: Outdoor unit.
C: Indoor unit.
D: Indoor unit address.
E: Either the current remote control switch (H-LINK) or the new one (H-LINK II) can be used.
F: Only the new remote control switch (H-LINK II) can be used.
N O T E
• The maximum number of indoor units than an H-LINK II can control is 160.
• If you use PSC-5S and the CSNET WEB 2.0 (systems only compatible with H-LINK) bear in mind that it will only rec-
ognize 16 indoor and 16 outdoor units.
Содержание RAS-(2-6)HVNP1(E)
Страница 2: ......
Страница 4: ... II ...
Страница 28: ......
Страница 134: ...4 Electrical wiring 120 SMGB0087 rev 0 12 2013 4 7 3 RAS 3HVNP1E 1 230V 50Hz XEK01261_0 ...
Страница 136: ...4 Electrical wiring 122 SMGB0087 rev 0 12 2013 4 7 4 RAS 4 6 HVNP1E 1 230V 50Hz XEK01262_1 ...
Страница 138: ...4 Electrical wiring 124 SMGB0087 rev 0 12 2013 4 7 6 RAS 4 6 HNP1E 3N 400V 50Hz XEK01263_2 ...
Страница 140: ...4 Electrical wiring 126 SMGB0087 rev 0 12 2013 4 7 7 RAS 4 6 HVNC1E 1 230V 50Hz XEK01264_4 ...
Страница 142: ...4 Electrical wiring 128 SMGB0087 rev 0 12 2013 4 7 8 RAS 4 6 HNC1E 3N 400V 50Hz XEK01265_4 ...
Страница 144: ...4 Electrical wiring 130 SMGB0087 rev 0 12 2013 4 7 10 RAS 8 10 HN P C E 3N 400V 50Hz XEK01288_3 ...
Страница 146: ...4 Electrical wiring 132 SMGB0087 rev 0 12 2013 4 7 12 RAS 12HN P C 3N 400V 50Hz 7T146440 ...
Страница 148: ......
Страница 204: ......
Страница 220: ......
Страница 332: ......
Страница 353: ...9 Spare parts 339 SMGB0087 rev 0 12 2013 9 RAS 8 10 HNCE Spare Parts Document EPN 201211D ...
Страница 354: ...9 Spare parts 340 SMGB0087 rev 0 12 2013 9 6 2 Electrical parts View from P Spare Parts Document EPN 201211D ...
Страница 362: ......
Страница 484: ......
Страница 496: ......
Страница 497: ......