8 Troubleshooting
210
SMGB0087 rev.0 - 12/2013
8.1.3 Abnormal transmission between the remote control switch and the indoor unit
•
RUN LED on the remote control switch:
Flickering every 2 seconds.
Phenomenon
Cause
Check item
Action
(Turn OFF the main switch)
Disconnection or insufficient contacting of the remote control
cable
Check the cable and the
connections
Repair the cable or connect the
cable
Failure of the remote control switch
Check the remote control
switch by means of the
self-check mode *1)
Replace the remote control
switch if the remote control
switch is faulty
Failure of PCB (in the indoor
unit and the remote control
switch)
Disconnected wire to PCB
Check the connectors
Correctly connect the wires
Failure of PCB
Check PCB by means of the
self-check mode *2)
Replace PCB if it failed
N O T E
• *1): Refer to section
“Self-checking procedure of the remote control switch”
• *2): Refer to section
“Self-checking procedure of PCB by means of the Remote Control Switch”
.
8.1.4 Abnormal operation of the devices
Phenomenon
Cause
Check item
Action
(Turn OFF the main switch)
RUN LED is ON and
the LCD is indicated.
However, the system
does not operate
(For example, the
indoor fan, the
outdoor fan or the
compressor does not
operate)
Failure of the indoor
unit fan motor
Disconnected coil
Measure the coil resistance
by means of the tester
Replace the Indoor unit fan
motor
Burnt-out coil
Measure the insulation
resistance
Failure of the outdoor
unit fan motor
Disconnected coil
Measure the coil resistance
by means of the tester
Replace the outdoor unit fan
motor
Burnt-out coil
Measure the insulation
resistance
Failure of the
magnetic switch for
the outdoor unit fan
motor
Insufficient contacting Measure the voltage
between the contacting parts
Replace PCB for the outdoor
unit
Failure of the comp. motor
Measure the resistance
between two wires
Replace the compressor
Failure of the compressor
Check for an abnormal
sound from the compressor
Failure of the mag-
netic switch for comp. Insufficient contacting
Check that the magnetic
switch activates correctly
or not
Replace the magnetic switch
Failure of one of
PCBs
Disconnected wiring
to PCB
Check the connections
Correctly connect the wiring
Failure of PCB
Check PCB by means of the
self-check mode *1)
Replace PCB if it failed
Содержание RAS-(2-6)HVNP1(E)
Страница 2: ......
Страница 4: ... II ...
Страница 28: ......
Страница 134: ...4 Electrical wiring 120 SMGB0087 rev 0 12 2013 4 7 3 RAS 3HVNP1E 1 230V 50Hz XEK01261_0 ...
Страница 136: ...4 Electrical wiring 122 SMGB0087 rev 0 12 2013 4 7 4 RAS 4 6 HVNP1E 1 230V 50Hz XEK01262_1 ...
Страница 138: ...4 Electrical wiring 124 SMGB0087 rev 0 12 2013 4 7 6 RAS 4 6 HNP1E 3N 400V 50Hz XEK01263_2 ...
Страница 140: ...4 Electrical wiring 126 SMGB0087 rev 0 12 2013 4 7 7 RAS 4 6 HVNC1E 1 230V 50Hz XEK01264_4 ...
Страница 142: ...4 Electrical wiring 128 SMGB0087 rev 0 12 2013 4 7 8 RAS 4 6 HNC1E 3N 400V 50Hz XEK01265_4 ...
Страница 144: ...4 Electrical wiring 130 SMGB0087 rev 0 12 2013 4 7 10 RAS 8 10 HN P C E 3N 400V 50Hz XEK01288_3 ...
Страница 146: ...4 Electrical wiring 132 SMGB0087 rev 0 12 2013 4 7 12 RAS 12HN P C 3N 400V 50Hz 7T146440 ...
Страница 148: ......
Страница 204: ......
Страница 220: ......
Страница 332: ......
Страница 353: ...9 Spare parts 339 SMGB0087 rev 0 12 2013 9 RAS 8 10 HNCE Spare Parts Document EPN 201211D ...
Страница 354: ...9 Spare parts 340 SMGB0087 rev 0 12 2013 9 6 2 Electrical parts View from P Spare Parts Document EPN 201211D ...
Страница 362: ......
Страница 484: ......
Страница 496: ......
Страница 497: ......