![Hitachi RAS-(2-6)HVNP1(E) Скачать руководство пользователя страница 490](http://html.mh-extra.com/html/hitachi/ras-2-6-hvnp1-e/ras-2-6-hvnp1-e_service-manual_2139503490.webp)
12 Maintenance notes
476
SMGB0087 rev.0 - 12/2013
12.3 Service and maintenance record
No.
Check item
Action
Judgement
1
Is the service area sufficient?
—
Yes
No
2
Is there a short circuit of the discharged air?
—
Yes
No
3
Any heat influence?
—
Yes
No
4
Is the ground wire connected?
—
Yes
No
5
Refrigerant piping.
—
Good
Not Good
6
Fixing the units.
—
Good
Not Good
7
Is there any damage on the outer surface or the
internal surface?
—
Yes
No
8
Checking the screw and the bolts.
Tighten if loosened.
Tightened
Not Tightened
9
Tightening the terminal screws.
Tighten all the terminal screws with a Phillips
screwdriver.
Tightened
Not Tightened
10
Are the compressor terminals tightly fixed?
Push all the terminals.
Pushed
Not Pushed
11
Insulation resistance.
Measure the insulation resistance with an insu-
lation resistance meter.
Compressor and fan.
Motor: greater than 3MΩ.
Others: greater than 3MΩ.
Good
Not Good
12
Does the drain water flow smoothly?
Check the smooth flow by pouring some water.
Good
Not Good
13
Check for a leakage in the compressor.
Check for any leakage.
Good
Not Good
14
Check for a leakage in the outdoor heat exchan-
ger.
Check for any leakage.
Good
Not Good
15
Check for a leakage in the indoor heat exchanger. Check for any leakage.
Good
Not Good
16
Check for a leakage in the 4-way valve.
Check for any leakage.
Good
Not Good
17
Check for a leakage in the check valve.
Check for any leakage.
Good
No Good
18
Check for a leakage in the accumulator.
Check for any leakage.
Good
Not Good
19
Check for a leakage in the strainer.
Check for any leakage.
Good
Not Good
20
Check for a leakage in the electronic expansion
valve
Check for any leakage.
Good
Not Good
21
Check for a leakage in the piping.
Check for any leakage.
Good
Not Good
22
Check the direction of the fans.
By viewing the airflow volume.
Good
Not Good
23
Voltage among each phase.
Higher than AC220V.
Good
Not Good
24
Vibration and sound.
Check the fan the compressor the piping and
others.
Good
Not Good
25
Activation of each operation mode.
Check the activation of the COOL switch the
HEAT switch the STOP switch and the TEMP
switch
Good
Not Good
26
High-pressure cut-out switch.
Check the actual activation value.
Good
Not Good
27
Check the activation of the drain-up mechanism. Check the activation during the cooling process.
Good
Not Good
28
Air inlet temperature of the indoor unit DB/WB.
—
(°C)DB
(°C)WB
29
Air outlet temperature of the indoor unit DB/WB.
—
(°C)DB
(°C)WB
30
Air inlet temperature of the outdoor unit DB/WB.
—
(°C)DB
(°C)WB
31
Air outlet temperature of the outdoor unit DB/WB.
—
(°C)DB
(°C)WB
32
High-pressure switch.
—
kg/cm
2
G
33
Low-pressure switch.
—
kg/cm
2
G
34
Operating voltage.
—
V
35
Operating current.
—
A
36
Instructions to the client for cleaning the air filter.
—
Done
Not yet
37
Instructions to the client about the cleaning
method.
—
Done
Not yet
38
Instructions to the client about the operation.
—
Done
Not yet
Содержание RAS-(2-6)HVNP1(E)
Страница 2: ......
Страница 4: ... II ...
Страница 28: ......
Страница 134: ...4 Electrical wiring 120 SMGB0087 rev 0 12 2013 4 7 3 RAS 3HVNP1E 1 230V 50Hz XEK01261_0 ...
Страница 136: ...4 Electrical wiring 122 SMGB0087 rev 0 12 2013 4 7 4 RAS 4 6 HVNP1E 1 230V 50Hz XEK01262_1 ...
Страница 138: ...4 Electrical wiring 124 SMGB0087 rev 0 12 2013 4 7 6 RAS 4 6 HNP1E 3N 400V 50Hz XEK01263_2 ...
Страница 140: ...4 Electrical wiring 126 SMGB0087 rev 0 12 2013 4 7 7 RAS 4 6 HVNC1E 1 230V 50Hz XEK01264_4 ...
Страница 142: ...4 Electrical wiring 128 SMGB0087 rev 0 12 2013 4 7 8 RAS 4 6 HNC1E 3N 400V 50Hz XEK01265_4 ...
Страница 144: ...4 Electrical wiring 130 SMGB0087 rev 0 12 2013 4 7 10 RAS 8 10 HN P C E 3N 400V 50Hz XEK01288_3 ...
Страница 146: ...4 Electrical wiring 132 SMGB0087 rev 0 12 2013 4 7 12 RAS 12HN P C 3N 400V 50Hz 7T146440 ...
Страница 148: ......
Страница 204: ......
Страница 220: ......
Страница 332: ......
Страница 353: ...9 Spare parts 339 SMGB0087 rev 0 12 2013 9 RAS 8 10 HNCE Spare Parts Document EPN 201211D ...
Страница 354: ...9 Spare parts 340 SMGB0087 rev 0 12 2013 9 6 2 Electrical parts View from P Spare Parts Document EPN 201211D ...
Страница 362: ......
Страница 484: ......
Страница 496: ......
Страница 497: ......