![Hitachi RAS-(2-6)HVNP1(E) Скачать руководство пользователя страница 201](http://html.mh-extra.com/html/hitachi/ras-2-6-hvnp1-e/ras-2-6-hvnp1-e_service-manual_2139503201.webp)
6 Optional functions
187
SMGB0087 rev.0 - 12/2013
6
Element
Optional function
Individual
setting
Settings
Setting conditions
Description
F6
Automatic reset
temperature for
heating
X
17
17 ºC
This function is used to set automatic
temperature release in HEAT mode.
18-20
(18-20) ºC
21
21 ºC
(factory setting)
25-28
(25-28) ºC
29
29 ºC
30
30 ºC
PC-ART: Not
available
–
17-30
Not available
–
F7
Operation stoppage
prevention by remote
control switch
operational error
(5)
X
00
Not activated
function
–
01
Activated function
PC-ART: Not
available
–
00-01
Not available
–
F8
Lock function for
operation mode
selection
X
00
Not activated
function
This function is used to prevent changes
to the operating mode.
01
Activated function
(factory setting)
F9
Lock function for
temperature setting
X
00
Not activated
function
This function is used to prevent changes
to the temperature setting.
01
Activated function
(factory setting)
FA
Lock function for fan
speed selection
X
00
Not activated
function
This function is used to prevent changes
to the fan speed.
01
Activated function
(factory setting)
Fb
Lock function for
swing louver
operation
X
00
Not activated
function
This function is used to prevent changes
to automatic louver operations.
01
Activated function
(factory setting)
FC
Lower limit of set-
ting temperature for
cooling
X
00
Standard
This function is used to define a lower
temperature setting limit for FAN/COOL/
DRY modes.
01
Lower limit +1 ºC
02
Lower limit +2 ºC
03-08
Lower limit
+(03-08) ºC
09
Lower limit +9 ºC
10
Lower limit +10 ºC
Fd
Upper limit of setting
temperature for heat-
ing
X
00
Standard
This function is used to define an upper
temperature setting limit for HEAT mode.
PC-ARF: up to -12 ºC
01
Lower limit -1 ºC
02
Lower limit -2 ºC
03-08
Lower limit
-(3~8) ºC
09
Lower limit -9 ºC
10
Lower limit -10 ºC
FE
Not available
–
00
Not available
Use at 00 conditions
–
01
02
Содержание RAS-(2-6)HVNP1(E)
Страница 2: ......
Страница 4: ... II ...
Страница 28: ......
Страница 134: ...4 Electrical wiring 120 SMGB0087 rev 0 12 2013 4 7 3 RAS 3HVNP1E 1 230V 50Hz XEK01261_0 ...
Страница 136: ...4 Electrical wiring 122 SMGB0087 rev 0 12 2013 4 7 4 RAS 4 6 HVNP1E 1 230V 50Hz XEK01262_1 ...
Страница 138: ...4 Electrical wiring 124 SMGB0087 rev 0 12 2013 4 7 6 RAS 4 6 HNP1E 3N 400V 50Hz XEK01263_2 ...
Страница 140: ...4 Electrical wiring 126 SMGB0087 rev 0 12 2013 4 7 7 RAS 4 6 HVNC1E 1 230V 50Hz XEK01264_4 ...
Страница 142: ...4 Electrical wiring 128 SMGB0087 rev 0 12 2013 4 7 8 RAS 4 6 HNC1E 3N 400V 50Hz XEK01265_4 ...
Страница 144: ...4 Electrical wiring 130 SMGB0087 rev 0 12 2013 4 7 10 RAS 8 10 HN P C E 3N 400V 50Hz XEK01288_3 ...
Страница 146: ...4 Electrical wiring 132 SMGB0087 rev 0 12 2013 4 7 12 RAS 12HN P C 3N 400V 50Hz 7T146440 ...
Страница 148: ......
Страница 204: ......
Страница 220: ......
Страница 332: ......
Страница 353: ...9 Spare parts 339 SMGB0087 rev 0 12 2013 9 RAS 8 10 HNCE Spare Parts Document EPN 201211D ...
Страница 354: ...9 Spare parts 340 SMGB0087 rev 0 12 2013 9 6 2 Electrical parts View from P Spare Parts Document EPN 201211D ...
Страница 362: ......
Страница 484: ......
Страница 496: ......
Страница 497: ......