7 Test run
201
SMGB0087 rev.0 - 12/2013
7
7.5 Test run procedure from the outdoor unit side
The test run procedure from the outdoor unit side is shown below.
You can set this DIP switch while the power source is ON.
Setting of dip switch
DSW1
1
Test Run
2
COOL/HEAT
(Setting ON: Heat Operation)
3
COOL / HEAT intermediate season
4
Manual Compressor stop
D A N G E R
• Do not touch any other electrical components while you are setting the switches on the PCB.
• Do not attach or detach the service access panel when the power source for the outdoor unit is ON and the
outdoor unit is operating.
• Set all the DIP switches of DSW1 to OFF after completing the test run.
Operation
Dip Switch Setting
Operation
Remarks
Test run
Setting of Operation Mode:
Cooling: Set DSW1-2 OFF.
Heating: Set DSW1-2 ON.
Starting Test Run:
Set DSW1-1 ON and the operation
is started after a few ~20 seconds.
Cooling
Heating
The indoor unit automatically start to
operate when the test run of the outdoor
unit is set.
The ON/OFF operation can be per-
formed from the remote control switch or
DSW1-1 of the outdoor unit.
Continuous operation during 2 hours
is performed without Thermo-OFF.
N O T E
•
TEST RUN operation time can be in-
creased depressing the time switch
in the Remote Control.
•
If is setting DSW1-3 ON, cooling/
heating intermediate season mode
is activaded.
•
Take care that the indoor units start
operation in accord with the test run
operation of the outdoor unit.
•
The test run is started from the outdo-
or unit and stopped from the remote
control switch, the test run function of
the remote control switch is cance-
lled. However, the test run function of
the outdoor unit is not cancelled
•
In case that the plural indoor units
are connected with one remote con-
trol switch, all the units start test run
operation at the same time, therefo-
re, turn the power source OFF for the
indoor units not to operate test run. In
this case, the “TEST RUN” indication
of the remote control switch may flic-
ker, and this is not abnormal.
•
The setting of DSW1 is not required
for the test run from the remote con-
trol switch.
Manual
OFF of
compressor
Setting:
Compressor Manual OFF:
Set DSW1-4 ON.
Compressor ON:
Set DSW1-4 OFF.
When DSW1-4 is ON during com-
pressor operation, the compressor stops
to operate immediately and the indoor
unit is under the condition of Thermo-
OFF.
When DSW1-4 is OFF, the com-
pressor starts to operate after the can-
cellation of 3-minutes guard.
•
Do not repeat compressor ON/OFF
frequently.
Содержание RAS-(2-6)HVNP1(E)
Страница 2: ......
Страница 4: ... II ...
Страница 28: ......
Страница 134: ...4 Electrical wiring 120 SMGB0087 rev 0 12 2013 4 7 3 RAS 3HVNP1E 1 230V 50Hz XEK01261_0 ...
Страница 136: ...4 Electrical wiring 122 SMGB0087 rev 0 12 2013 4 7 4 RAS 4 6 HVNP1E 1 230V 50Hz XEK01262_1 ...
Страница 138: ...4 Electrical wiring 124 SMGB0087 rev 0 12 2013 4 7 6 RAS 4 6 HNP1E 3N 400V 50Hz XEK01263_2 ...
Страница 140: ...4 Electrical wiring 126 SMGB0087 rev 0 12 2013 4 7 7 RAS 4 6 HVNC1E 1 230V 50Hz XEK01264_4 ...
Страница 142: ...4 Electrical wiring 128 SMGB0087 rev 0 12 2013 4 7 8 RAS 4 6 HNC1E 3N 400V 50Hz XEK01265_4 ...
Страница 144: ...4 Electrical wiring 130 SMGB0087 rev 0 12 2013 4 7 10 RAS 8 10 HN P C E 3N 400V 50Hz XEK01288_3 ...
Страница 146: ...4 Electrical wiring 132 SMGB0087 rev 0 12 2013 4 7 12 RAS 12HN P C 3N 400V 50Hz 7T146440 ...
Страница 148: ......
Страница 204: ......
Страница 220: ......
Страница 332: ......
Страница 353: ...9 Spare parts 339 SMGB0087 rev 0 12 2013 9 RAS 8 10 HNCE Spare Parts Document EPN 201211D ...
Страница 354: ...9 Spare parts 340 SMGB0087 rev 0 12 2013 9 6 2 Electrical parts View from P Spare Parts Document EPN 201211D ...
Страница 362: ......
Страница 484: ......
Страница 496: ......
Страница 497: ......