6 Optional functions
168
SMGB0087 rev.0 - 12/2013
6.1.4 Description of optional signals
Input signals
N O T E
In brackets control function numbers.
a. Fixing operation mode (heating / cooling)(1/2)
This input function is fixed in terminals CN1 or CN2 of the PCB of the outdoor unit, to use it as a cooling and heating mode.
CN1 must be set up as follows.
Short circuit between the terminals 1 and 2 of CN1: set heating mode.
Short circuit between the terminals 2 and 3 of CN1: set cooling mode.
After having pre-fixed the established mode, the remote control can only be used to adjust the temperatures. Stoppage
code “d1” “20” will be displayed if an attempt is made to change the operation mode of any of the indoor units with the
remote control.
Example of wiring diagram of fixing the operation mode.
A
Outdoor unit PCB
• A: 3P connector cable.
• X1: Cooling.
• X2: Heating.
• SS1: Fixing operation mode switch.
• SS2: Change over switch
b. Demand thermo OFF (3
)
This is an input function to control the maximum power that the compressor can consume. When this option is turned on,
the outdoor units are stopped completely, and the indoor units go into thermo-OFF. Alarm “10” is displayed on the remote
control. If the switch of this function is disconnected it becomes available again.
Connect the cabling and use the materials as shown in
”6.1.1 Available ports”
.
N O T E
For single connection (only for cooling or heating input signal), this setting is not required.
c. Intermittent Operation of outdoor fan (4) for (RAS-(4-6)H(V)C1E only
This is an auxiliary function to protect the outdoor unit from snow. When the input terminals for “Intermittent Operation of
Outdoor Fan Motor” on the outdoor unit PCB are short-circuited during the compressor stoppage, all the outdoor fan motors
start operating. If the compressor restarts operating, the outdoor fan motors will be restored to normal operation. If the input
terminals of “Intermittent Operation of Outdoor Fan Motor” are opened during the outdoor fan motor operation following
the short circuit of these terminals, the outdoor fan motor will stop.This function is available only during the compressor
stoppage (during the compressor power-ON or thermo-OFF). Therefore, this function will not be available even if the input
signal is sent during the normal cooling or heating operation.
Содержание RAS-(2-6)HVNP1(E)
Страница 2: ......
Страница 4: ... II ...
Страница 28: ......
Страница 134: ...4 Electrical wiring 120 SMGB0087 rev 0 12 2013 4 7 3 RAS 3HVNP1E 1 230V 50Hz XEK01261_0 ...
Страница 136: ...4 Electrical wiring 122 SMGB0087 rev 0 12 2013 4 7 4 RAS 4 6 HVNP1E 1 230V 50Hz XEK01262_1 ...
Страница 138: ...4 Electrical wiring 124 SMGB0087 rev 0 12 2013 4 7 6 RAS 4 6 HNP1E 3N 400V 50Hz XEK01263_2 ...
Страница 140: ...4 Electrical wiring 126 SMGB0087 rev 0 12 2013 4 7 7 RAS 4 6 HVNC1E 1 230V 50Hz XEK01264_4 ...
Страница 142: ...4 Electrical wiring 128 SMGB0087 rev 0 12 2013 4 7 8 RAS 4 6 HNC1E 3N 400V 50Hz XEK01265_4 ...
Страница 144: ...4 Electrical wiring 130 SMGB0087 rev 0 12 2013 4 7 10 RAS 8 10 HN P C E 3N 400V 50Hz XEK01288_3 ...
Страница 146: ...4 Electrical wiring 132 SMGB0087 rev 0 12 2013 4 7 12 RAS 12HN P C 3N 400V 50Hz 7T146440 ...
Страница 148: ......
Страница 204: ......
Страница 220: ......
Страница 332: ......
Страница 353: ...9 Spare parts 339 SMGB0087 rev 0 12 2013 9 RAS 8 10 HNCE Spare Parts Document EPN 201211D ...
Страница 354: ...9 Spare parts 340 SMGB0087 rev 0 12 2013 9 6 2 Electrical parts View from P Spare Parts Document EPN 201211D ...
Страница 362: ......
Страница 484: ......
Страница 496: ......
Страница 497: ......